16
Sun Blade 6048 Modular System Product Notes • April 2011
■
Deselect it if your chassis does not have a cooling door.
The status changes to indicate your selection.
▼
To Configure the Sun Cooling Door Policy Using
the CLI
1. Log in to ILOM. Open a terminal window and type:
$
ssh root@
serveripaddress
Password:
password
The default password for the
root
account is
changeme
.
The ILOM CLI prompt appears (
->
).
2. Enter the command:
->
set /CMM/policy/COOLING_DOOR_INSTALLED=
selection
where
selection
:
enabled
if your chassis has a cooling door
disabled
if your chassis does not have a cooling door
The following display shows the policy settings with the cooling door disabled:
-> cd
/CMM/policy
/CMM/policy
->
show
/CMM/policy
Targets:
Properties:
COOLING_DOOR_INSTALLED = disabled
MONITOR_PS0_SIDE0 = enabled
MONITOR_PS0_SIDE1 = enabled
MONITOR_PS0_SIDE2 = enabled
MONITOR_PS1_SIDE0 = enabled
MONITOR_PS1_SIDE1 = enabled
MONITOR_PS1_SIDE2 = enabled
Commands:
cd
set
show
->