background image

Sun Microsystems, Inc.
www.sun.com

Submit comments about this document at:

http://www.sun.com/hwdocs/feedback

Sun Netra

CP3250

Blade Server User’s Guide

Part No. 820-5195-11
April 2009, Revision 01

Summary of Contents for Sun Netra CP3250

Page 1: ...Sun Microsystems Inc www sun com Submit comments about this document at http www sun com hwdocs feedback Sun Netra CP3250 Blade Server User s Guide Part No 820 5195 11 April 2009 Revision 01...

Page 2: ...Inc 4150 Network Circle Santa Clara California 95054 Etats Unis Tous droits r serv s Cette distribution peut comprendre des composants d velopp s par des tierces parties Des parties de ce produit pour...

Page 3: ...1 7 1 4 1 AMC 1 8 1 4 2 Advanced Rear Transition Module 1 8 1 5 Hot Swap Support 1 11 1 6 System Components 1 11 1 6 1 Required Hardware Components 1 11 1 6 2 Optional Hardware Components 1 12 1 6 3...

Page 4: ...2 2 Installing Optional Components 2 7 2 2 2 3 Configuring the Advanced Rear Transition Module ARTM 2 7 2 2 3 Installing the Netra CP3250 Blade Server in an ATCA Shelf 2 8 2 2 3 1 Installing an Advan...

Page 5: ...CMOS Setting Using Jumper 2 2 31 2 3 10 2 Changing the OOS LED Color Using Jumper 13 2 32 2 3 11 Checking DIP Switch Settings 2 33 2 3 12 Resetting the Netra CP3250 Blade Server 2 34 3 Hardware Archit...

Page 6: ...r 1 GbE or 10 GbE Switches 4 4 5 Configuring and Using BIOS Firmware 5 1 5 1 About BIOS Settings 5 2 5 1 1 Navigating BIOS Screens 5 2 5 1 2 BIOS Option ROMs 5 2 5 1 3 Description of the BIOS Screens...

Page 7: ...Zone 1 B 6 B 3 4 Data Transport Connector Zone 2 B 8 B 3 5 Advanced Rear Transition Module ARTM Connector Zone 3 B 9 B 3 5 1 Zone 3 J30 Connector Pin Assignments B 10 B 3 5 2 Zone 3 J31 Connector PIN...

Page 8: ...viii Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 9: ...n the ARTM 2 10 FIGURE 2 3 Engaging the Netra CP3250 Blade Server Latch 2 12 FIGURE 2 4 Serial Port on the Netra CP3250 Blade Server 2 14 FIGURE 2 5 Locating DIMM Slots 2 20 FIGURE 2 6 Installing a DI...

Page 10: ...ation Menu A 8 FIGURE A 8 Remote Access Configuration Menu A 9 FIGURE A 9 PCI Option ROM Configuration Menu A 10 FIGURE A 10 Trusted Computing Menu A 11 FIGURE A 11 Boot Settings Menu A 12 FIGURE A 12...

Page 11: ...9 TABLE B 1 Ethernet Port Connector Pin Assignments B 3 TABLE B 2 USB Port Pin Assignments B 4 TABLE B 3 Serial Port Mini DIN 8 pin Connector Pinouts B 5 TABLE B 4 Power Distribution Connector Pin As...

Page 12: ...xii Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 13: ...perating systems and Advanced Telecommunications Computing Architecture ATCA computing environment How This Document Is Organized Chapter 1 provides an overview of the Sun Netra CP3250 blade server Ch...

Page 14: ...system booting the system and configuring devices Refer to the following for this information Software documentation that you received with your system Solaris Operating System documentation which is...

Page 15: ...nd directories on screen computer output Edit your login file Use ls a to list all files You have mail AaBbCc123 What you type when contrasted with on screen computer output su Password AaBbCc123 Book...

Page 16: ...onfiguration Sun Netra CP32x0 SAS Storage Advanced Rear Transition Module Dual HD User s Guide 820 3147 PDF HTML Online http docs sun com app docs prod cp32x0 sas hic Installation and Configuration Su...

Page 17: ...iable for any actual or alleged damage or loss caused by or in connection with the use of or reliance on any such content goods or services that are available on or through such sites or resources Sun...

Page 18: ...xviii Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 19: ...er This chapter contains the following sections Section 1 1 Overview on page 1 2 Section 1 2 Features on page 1 2 Section 1 3 Physical Description on page 1 4 Section 1 4 System Configurations on page...

Page 20: ...elines PICMG 3 1 which builds on the PICMG 3 0 base specification and on IEEE 802 3 2003 1 2 Features The blade server s primary features are as follows ATCA card 322 25 mm x280 mm 1 2 inch slot heigh...

Page 21: ...upport using on board IPM controller Renesas H8 that provides dual IPMB bus The IPMB bus is to be monitored by the shelf manager providing redundant IPMI channels Rear I O expansion connectivity provi...

Page 22: ...1 4 Sun Netra CP3250 Blade Server User s Guide April 2009 1 3 Physical Description 1 3 1 Front Panel Components FIGURE 1 1 Netra CP3250 Blade Server Front View...

Page 23: ...Chapter 1 Overview 1 5 Figure Legend 1 Locking screws 2 Latches 3 Out of service OOS LED 4 OK LED 5 AMC slot 6 10 100 1000 Ethernet management port 7 Serial port 8 USB port 9 Reset button...

Page 24: ...ver User s Guide April 2009 1 3 2 Blade Server Diagram FIGURE 1 2 Netra CP3250 Blade Server Component Side View Figure Legend 1 CF card slot 4 Zone 1 power connector 2 Zone 3 connectors 5 DIMMs 3 Zone...

Page 25: ...loyed in various electrical configurations to suit user requirements For example the blade server can be configured to boot from a network as a diskless client with either a front panel or ARTM networ...

Page 26: ...fined by the AMC specification 1 4 2 Advanced Rear Transition Module You can install one of the optional Netra CP32x0 advanced rear transition modules ARTMs into the rear of the ATCA shelf opposite th...

Page 27: ...erview 1 9 FIGURE 1 4 Netra CP3250 Blade Server Backplane and Relationship to ARTM Note When using the ARTM with the Sun Netra CP3250 blade server use cables of less than 10 meters in length for seria...

Page 28: ...Configurations I O Hardware Required Description Ethernet Netra CP32x0 ARTM as an option for rear access The default boot path uses an Ethernet port the blade server runs in a diskless client configur...

Page 29: ...board shelf manager and power supply Console output device or serial terminal Boot device such as hard drive network or Compact Flash card Peripheral device for network access IPMC built in Cables for...

Page 30: ...able of operating at 10 GbE but is set by default to operate at 1GbE To use the switch at 10 GbE perform a one time configuration procedure available in the Sun Netra CP3x40 Switch Product Notes 820 3...

Page 31: ...e rest of the world please find the World Wide Solution Center nearest you at the following web site http www sun com contact services_solutions jsp When you call Sun Services be sure to indicate if t...

Page 32: ...ode form It is an orange label located on the Zone 1 connector FIGURE 1 5 Netra CP3250 Blade Server Barcode Labeling 1 7 2 Viewing the Electronic Blade Server ID Information The Sun Netra CP3250 blade...

Page 33: ...ber for the FRU level assembly of the blade server This assembly level is equivalent to the FRU replacement that is received from Sun Service Mfg Date Time Date Time of blade server assembly Manufactu...

Page 34: ...1 16 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 35: ...he Sun Netra CP3250 blade server hardware installation and service procedures This chapter contains the following sections Section 2 1 Safety and Tool Requirements on page 2 2 Section 2 2 Installing t...

Page 36: ...th commonly accepted procedures for integrating electronic systems and the general practice of Sun systems integration and administration Although parts of these systems are designed for hot swap oper...

Page 37: ...vers that are out of their antistatic bags on an antistatic mat if one is available and the mat is grounded to a facility electrical service ground Do not place blade servers on top of an antistatic b...

Page 38: ...n 2 2 1 2 Local Network IP Addresses and Host Names Worksheet on page 2 5 5 Ensure that the host names and their network IP addresses are allocated and registered at the site Record this information i...

Page 39: ...the blade server You can also find it on the barcode label on the node blade server see Section 1 7 1 Locating the Part Number and Serial Number Information on page 1 13 TABLE 2 1 Local Area Network I...

Page 40: ...peripheral boards into the ATCA shelf Section 2 2 3 Installing the Netra CP3250 Blade Server in an ATCA Shelf on page 2 8 4 Connecting the nodes to a local network Section 2 2 4 Connecting External I...

Page 41: ...onal Components Use the following table to locate your options and installation instructions 2 2 2 3 Configuring the Advanced Rear Transition Module ARTM If you are using one of the Netra advanced rea...

Page 42: ...information see Section 1 4 2 Advanced Rear Transition Module on page 1 8 1 Verify that you have taken the necessary antistatic precautions See Section 2 1 1 Equipment and Operator Safety on page 2 2...

Page 43: ...a Netra CP32x0 ARTM 3 Remove the slot filler panel from the selected slot if necessary 4 Retrieve the advanced rear transition module ARTM from the ship kit 5 Prepare the rear transition module by op...

Page 44: ...uides in the appropriate slot Look into the enclosure to verify correct alignment of the rails in the guides 7 Keep the ARTM aligned in the guides and slide the module in until the injector ejector la...

Page 45: ...fe place you might need to use it again if you remove a blade server for an extended time 3 Prepare the Sun Netra CP3250 blade server by opening the injector ejector latches 4 Carefully align the edge...

Page 46: ...nd the top and the bottom of the Sun Netra CP3250 blade server to ensure that it is secured to the ATCA shelf FIGURE 2 2 The blade server is now completely installed and will power on automatically 8...

Page 47: ...tach asynchronous serial I O cables from serial communication devices to the RJ 45 serial ports on the Sun Netra CP3250 blade server or Netra CP32x0 ARTM 2 2 4 1 Connecting Cables to a System Console...

Page 48: ...Guide April 2009 FIGURE 2 4 Serial Port on the Netra CP3250 Blade Server 3 Use one of the following to establish a full duplex serial terminal connection with the Sun Netra CP3250 blade server The ti...

Page 49: ...serving as the system console 3 Set the serial communications settings to 9600 baud 8 bit 1 stop bit no parity and no handshake 2 2 4 3 Netinstall Boot Device Map TABLE 2 2 provides a map of netinsta...

Page 50: ...4f xx xn 5 nxge1 Sun 10 GbE Multithreaded Networking Technolgy 10 GB Extended Fabric 1 Slot 8 0 14 4f xx xn 6 nxge2 Sun 10 GbE Multithreaded Networking Technolgy 1 GB AMC and ARTM 0 14 4f xx xn 7 nxg...

Page 51: ...e blade server See Section 2 3 3 Removing the Netra CP3250 Blade Server on page 2 18 2 3 2 Powering Off the Netra CP3250 Blade Server 1 Shut down the operating system Log in and shut down any OS opera...

Page 52: ...server from the ATCA shelf and place the blade server on an antistatic mat 2 3 4 Powering On the System Sun Netra CP3250 blade servers are powered on automatically via the H8 BMC when you install the...

Page 53: ...ommodates the following DIMMs and configurations Up to six standard DDR2 SDRAM registered ECC DIMMs DIMMs must be installed in matching pairs 2 GB and 4 GB DDR2 modules are supported Maximum of 24 GB...

Page 54: ...009 FIGURE 2 5 Locating DIMM Slots Populate DIMMs in matching pairs starting with Pair 0 then adding Pair 1 then Pair 2 There are two channels Channel A and Channel B DIMMs are identified as A0 B0 A1...

Page 55: ...connectors on the Sun Netra CP3250 blade server Select the connectors where you will install the DIMM See FIGURE 2 5 for DIMM slot locations Caution Do not remove the DIMM from its antistatic contain...

Page 56: ...e DIMM until its bottom edge the edge with the gold fingers is firmly seated in the connector FIGURE 2 6 Installing a DIMM 6 Press the top edge of the DIMM toward the blade server until the retainer c...

Page 57: ...from the shelf as explained in Section 2 3 3 Removing the Netra CP3250 Blade Server on page 2 18 Remove the Sun Netra CP3250 blade server from its antistatic envelope and place it on an ESD mat near t...

Page 58: ...0 blade server is installed in an ATCA shelf 1 Access the blade server by performing one of the following procedures If the Sun Netra CP3250 blade server is installed in an ATCA shelf remove the blade...

Page 59: ...t provides access to the Compact Flash then open the door FIGURE 2 8 shows the door FIGURE 2 8 Opening the Door to Access Compact Flash 3 Locate the Compact Flash connector The connector is located on...

Page 60: ...all the Compact Flash card use the arrow on the card as a guide to insert the card into the Compact Flash connector Note Sun Compact Flash cards have a life time of 2 000 000 write erase cycles Users...

Page 61: ...Netra CP3250 blade server is installed in the chassis Note The following procedure provides a general set of instructions for installing an AMC on the Sun Netra CP3250 blade server Refer to the AMC ma...

Page 62: ...ade Server User s Guide April 2009 FIGURE 2 10 Removing an AMC Filler Panel 4 Retrieve the AMC from its shipping kit and place it on an antistatic surface 5 Insert the AMC through the cutout and into...

Page 63: ...t use excessive force when installing the AMC into the slot You might damage the AMC connector on the Sun Netra CP3250 blade server causing permanent damage to the AMC or the blade server If the AMC d...

Page 64: ...settings to be preserved in the event of power loss obtain and install the battery The battery must be type CR1632 with a minimum of 4ma abnormal charging current rating for example a Renata CR1632 C...

Page 65: ...the default BIOS settings Jumper 2 is shown in FIGURE 2 12 The jumper housing should be stored in the P2 P3 position which is the run position FIGURE 2 12 Jumper 2 in the Default Run Position TABLE 2...

Page 66: ...2 Installing the Blade Server Into the Shelf on page 2 11 Note The blade server will operate normally only when the jumper housing is in the run position 2 3 10 2 Changing the OOS LED Color Using Jump...

Page 67: ...11 Checking DIP Switch Settings DIP switch settings are set by default at the factory The following settings are required for normal operation of the blade server FIGURE 2 13 SW1 Default DIP Switch S...

Page 68: ...thout all fans component heatsinks air baffles and covers installed Severe damage to components can occur if the ATCA shelf is operated without adequate cooling mechanisms 1 Use a spudger tool or othe...

Page 69: ...Chapter 2 Hardware Installation and Service 2 35 FIGURE 2 16 Netra CP3250 Blade Server Front Panel Reset button...

Page 70: ...2 36 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 71: ...Netra CP3250 blade server This chapter contains the following sections Section 3 1 Block Diagram on page 3 2 Section 3 2 Intel Processors on page 3 3 Section 3 3 Intel San Clemente MCH on page 3 3 Se...

Page 72: ...3 2 Sun Netra CP3250 Blade Server User s Guide April 2009 3 1 Block Diagram...

Page 73: ...Enhanced 36 bit memory addressing FSB address data and response parity protection Enhanced Intel Speedstep Technology Intel Advanced Thermal Manager Streaming SIMD Extensions 3 SSE3 Support Embedded l...

Page 74: ...troller supports 1 bit per byte ECC and supports DDR2 667 registered DRR SDRAM modules For more information on supported DIMM configurations see Section 2 3 6 1 DIMM Requirements on page 2 19 Addition...

Page 75: ...O also includes integrated USB 2 0 and USB 1 0 support an LPC interface a system management interface a power management interface PECI interface integrated Gigabit Ethernet controllers not used on S...

Page 76: ...d in SMM handler and to support wake up and other power state transitions The design meets LPC 1 0 design guidelines The LPC bus provides system connectivity to the following devices Redundant BIOS TP...

Page 77: ...to IPMB 0 Hot swap latch input and LED control Payload power control Payload base and fabric interface e keying control Payload power and temperature monitoring 3 5 7 RS 232 Serial Ports A Serial por...

Page 78: ...hernet connections to the ATCA backplane extended fabric where four lanes are driven at 3 125 Gbyte sec if the ATCA switch supports 10 Gbit Ethernet or a single lane at 1 25 Gbyte sec if the switch is...

Page 79: ...S SATA The Sun Netra CP3250 blade server supports AMC drives SAS or SATA that contain their own PCIe based controller chip connecting to the system via the PCIe Bus The Sun Netra CP3250 blade server s...

Page 80: ...3 10 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 81: ...contains the following sections Section 4 1 Operating Systems on page 4 2 Section 4 2 Software Updates on page 4 2 Section 4 3 SunVTS Software on page 4 3 Section 4 4 Configuring Sun Netra CP3250 blad...

Page 82: ...e appropriate Solaris Documentation Collection at the Sun Documentation web site at http docs sun com For information on the WindRiver Linux RedHat Linux and Windows operating systems see the document...

Page 83: ...ances and processor affinity features You can perform high level system testing by using the appropriate version of SunVTS software For detailed information on SunVTS software support and downloads re...

Page 84: ...h and ARTM configurations The nxge conf file is located in the platform i86pc kernel drv directory The following examples show the proper entries for each switch configuration Example 1 When extended...

Page 85: ...Configuration of a BIOS Menu Item on page 5 3 Section 5 3 Setting the Boot Device Using BIOS Setup Screens on page 5 4 Section 5 4 Setting Supervisor and User Passwords on page 5 5 Section 5 5 Resett...

Page 86: ...OS Screens The BIOS Setup utility contains menu screens see Appendix A for illustrations of the screens Use the left and right arrow keys to move sequentially through the BIOS screens Fields that can...

Page 87: ...F2 key while the system is performing the power on self test POST See TABLE 5 1 for summary descriptions of the BIOS screens The first BIOS Setup menu screen is displayed 2 Highlight the field to be...

Page 88: ...page 5 3 for descriptions of the first level BIOS menu screens See Appendix A for illustrations of the BIOS screens 1 Use terminal emulation software to configure the serial COM1 settings Use the ANS...

Page 89: ...ss level for the User password 1 To reset any BIOS passwords clear the CMOS settings by resetting Jumper 2 See Section 2 3 10 1 Clearing the CMOS Setting Using Jumper 2 on page 2 31 for details 2 Ente...

Page 90: ...ey 4 Use the arrow keys to return to the BIOS Main Menu 5 Use the arrow keys to move down the main menu and reset the System Time and System Date fields 6 Use the arrow keys to move to the Exit Menu 7...

Page 91: ...nlikely case where the primary BIOS becomes corrupt If the primary BIOS becomes unbootable use the secondary BIOS to manually boot the blade server 1 Log into the Shelf Manager 2 To select the seconda...

Page 92: ...e Section 2 3 12 Resetting the Netra CP3250 Blade Server on page 2 34 5 9 Power On Self Test The system provides a rudimentary power on self test POST that runs each time the blade server boots to che...

Page 93: ...u screen is displayed 2 From the BIOS Main Menu screen select the Boot menu 3 From the Boot Settings screen select Boot Settings Configuration 4 On the Boot Settings Configuration screen you can enabl...

Page 94: ...5 10 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 95: ...A 1 APPENDIX A BIOS Screens This appendix provides examples of the screens from the BIOS utility For information on how to access BIOS menus and configure settings see Chapter 5...

Page 96: ...A 2 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 1 BIOS Main Menu...

Page 97: ...Appendix A BIOS Screens A 3 FIGURE A 2 Advanced Configuration Menu...

Page 98: ...A 4 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 3 CPU Configuration Menu...

Page 99: ...Appendix A BIOS Screens A 5 FIGURE A 4 IDE Configuration Menu...

Page 100: ...A 6 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 5 USB Configuration Menu...

Page 101: ...Appendix A BIOS Screens A 7 FIGURE A 6 Event Log Control Menu...

Page 102: ...A 8 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 7 IPMI 2 0 Configuration Menu...

Page 103: ...Appendix A BIOS Screens A 9 FIGURE A 8 Remote Access Configuration Menu...

Page 104: ...A 10 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 9 PCI Option ROM Configuration Menu...

Page 105: ...Appendix A BIOS Screens A 11 FIGURE A 10 Trusted Computing Menu...

Page 106: ...A 12 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 11 Boot Settings Menu...

Page 107: ...Appendix A BIOS Screens A 13 FIGURE A 12 Boot Device Priority Configuration Menu...

Page 108: ...A 14 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 13 Security Settings Menu...

Page 109: ...Appendix A BIOS Screens A 15 FIGURE A 14 Exit Menu...

Page 110: ...A 16 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 111: ...ristics Specifications for the Sun Netra CP3250 blade server are provided in the following sections Section B 1 Form Factor on page B 2 Section B 2 Power and Thermal Metrics on page B 2 Section B 3 Co...

Page 112: ...es 25W to ARTM 20W to AMC and two Intel Harpertown CPUs 5C 55C for NEBS compliance Power input 36 VDC to 72 VDC 48VDC nominal CPU temperature thresholds are set relative to the Thermal Control Circuit...

Page 113: ...either 10 BASE T 100 BASE T or 1000 BASE T FIGURE B 1 shows the Ethernet port connector FIGURE B 1 Ethernet RJ 45 Connector TABLE B 1 provides the eight pin assignments for the Ethernet port connecto...

Page 114: ...2 shows the connector pin assignments for both of the front panel USB ports FIGURE B 2 Front Panel USB Connector TABLE B 3 lists the USB port connector pin assignments TABLE B 2 USB Port Pin Assignme...

Page 115: ...try standard specification PICMG Advanced Mezzanine Cards AMC 0 Specification R1 0 ECR 002 D0 9 June 29 2006 The AMC slot is available at the front panel The AMC can be accessed from the front panel d...

Page 116: ...The analog test and ring voltage pins are left unconnected FIGURE B 4 shows the pin assignments FIGURE B 4 Power Distribution Connector Zone 1 P10 TABLE B 4 lists the power distribution connector pin...

Page 117: ...ging Generator A Negative Ringing 20 RING_B Ringing Generator B Negative Ringing 21 MT1_RING Metallic Test 1 Ringing 22 MT2_RING Metallic Test 2 Ringing 23 RING_A Ringing Generator AReturn 24 RING_B R...

Page 118: ...ase fabric channels four differential signal pairs each 16 signals total Two 10 Gbit SERDES ports on the extended fabric eight differential signal pairs each 32 signals total The connector vendor part...

Page 119: ...ARTM is the signal receiver Similarly RX means the ATCA blade is the signal receiver and the ARTM is the signal source The reserved pins indicate connector pins that are currently reserved for compat...

Page 120: ...ND Shelf_GND long First TABLE B 6 J31 Connector Pin Assignments Row Interface AB BG CD DG EF FG 1 AMC0 EO RTM_TX13 AMC0 EO_Rx1 RTM_TX13 AMC0 EO_Rx1 GND RTM_RX 12 AMC0 EO_Tx0 RTM_RX 12 AMC0 EO_Tx0 GND...

Page 121: ...ved GND Reserved Reserved GND Reserved Reserved GND TABLE B 7 J32 Connector Pin Assignments Row Interface AB BG CD DG EF FG 1 Reserved Reserved Reserved GND Reserved Reserved GND Reserved Reserved GND...

Page 122: ...1 PCIe x8 Lane PETx0 PETx0 GND PERx0 PERx0 GND FCLKA FCLKA GND 2 PCIe x8 Lane PETx1 PETx1 GND PERx1 PERx1 GND TCLKA TCLKA GND 3 PCIe x8 Lane PETx2 PETx2 GND PERx2 PERx2 GND TCLKB TCLKB GND 4 PCIe x8 L...

Page 123: ...D Frame Chassis Safety Ground Logic_GND Logic 0vdc Logic Ground Common return for Management Power Payload Power reference potential for single ended logic signaling and shielding for differential pai...

Page 124: ..._TX GBEthernet SerDes transmit differential pair signals SLAN_RX GBEthernet SerDes receive differential pair signals PETx PCI Express transmit differential pair signals PERx PCI Express receive differ...

Page 125: ...Appendix B Physical Characteristics B 15...

Page 126: ...B 16 Sun Netra CP3250 Blade Server User s Guide April 2009...

Page 127: ...mands This appendix provides information about using the ShMM CLI and most commonly used ShMM commands This appendix contains the following topics Shelf Manager Command Line Interface on page 2 Shelf...

Page 128: ...rrent sensor values threshold settings recent events and overall shelf health To Start the Command Line Interface 1 To use the CLI first log on to the Linux operation system on the shelf management ca...

Page 129: ...r the web site URL see Related Documentation on page xv clia Pigeon Point Shelf Manager Command Line Interpreter CLI ipmc 20 20 Entity d0 0 Maximum FRU device ID 20 PICMG Version 2 0 Hot Swap State M4...

Page 130: ...device ID Provides user friendly FRU Information output getthreshold threshold IPMB address optional sensor name optional sensor number optional Shows threshold information about a specific sensor hel...

Page 131: ...de servers Blade server names are assigned to slot numbers shelf subcommand with its parameters Shows general information about the shelf several subcommands allow setting shelf attributes and getting...

Page 132: ...user to determine whether a specific command is being executed on the active or on the backup Shelf Manager the following message is issued when a CLI command is executed on the backup Shelf Manager...

Page 133: ...Access Configuration A 9 Security Settings A 14 Boot Setting menu A 12 Boot Settings Configuration menu A 13 booting 1 7 C cabling 2 14 installing 2 13 system console 2 15 system console for Solaris 2...

Page 134: ...2 15 networking and I O 3 5 O operating system compatibility 4 2 P part number locating 1 14 password changing BIOS 5 5 PCI Express Configuration menu A 10 pinouts B 2 pinouts serial port B 5 POST ch...

Reviews: