Chapter 2
Hardware Installation and Service
2-17
2.3
Service Procedures
2.3.1
Hot-Swapping the Netra CP3250 Blade Server
You can remove the Sun Netra CP3250 blade server without powering off the entire
chassis by performing these steps.
1. Power off the blade server.
See
Section 2.3.2, “Powering Off the Netra CP3250 Blade Server” on page 2-17
.
2. Remove the blade server.
See
Section 2.3.3, “Removing the Netra CP3250 Blade Server” on page 2-18
.
2.3.2
Powering Off the Netra CP3250 Blade Server
1. Shut down the operating system.
Log in and shut down any OS operating on the blade server or its companion
ARTM.
2. Deactivate the blade server.
Log in to the shelf manager and deactivate the blade server in the target slot.
For example, to shut down the blade server in slot 3, log in to the shelf manager
and type:
Wait for the blue Hot-Swap LED to light steadily before removing the blade
server.
#
clia deactivate board 3
Summary of Contents for Sun Netra CP3250
Page 8: ...viii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 12: ...xii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 18: ...xviii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 34: ...1 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 70: ...2 36 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 72: ...3 2 Sun Netra CP3250 Blade Server User s Guide April 2009 3 1 Block Diagram...
Page 80: ...3 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 94: ...5 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 96: ...A 2 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 1 BIOS Main Menu...
Page 97: ...Appendix A BIOS Screens A 3 FIGURE A 2 Advanced Configuration Menu...
Page 98: ...A 4 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 3 CPU Configuration Menu...
Page 99: ...Appendix A BIOS Screens A 5 FIGURE A 4 IDE Configuration Menu...
Page 100: ...A 6 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 5 USB Configuration Menu...
Page 101: ...Appendix A BIOS Screens A 7 FIGURE A 6 Event Log Control Menu...
Page 103: ...Appendix A BIOS Screens A 9 FIGURE A 8 Remote Access Configuration Menu...
Page 105: ...Appendix A BIOS Screens A 11 FIGURE A 10 Trusted Computing Menu...
Page 106: ...A 12 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 11 Boot Settings Menu...
Page 107: ...Appendix A BIOS Screens A 13 FIGURE A 12 Boot Device Priority Configuration Menu...
Page 108: ...A 14 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 13 Security Settings Menu...
Page 109: ...Appendix A BIOS Screens A 15 FIGURE A 14 Exit Menu...
Page 110: ...A 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 125: ...Appendix B Physical Characteristics B 15...
Page 126: ...B 16 Sun Netra CP3250 Blade Server User s Guide April 2009...