Chapter 5
Configuring and Using BIOS Firmware
5-7
5.7
Secondary BIOS Image
The Sun Netra CP3250 blade server provides dual 1-Mbyte BIOS chips that support
redundant BIOS images for increased reliability. The default chip (page 0) acts as the
primary BIOS chip and is automatically selected for update during a firmware
upgrade. The secondary BIOS chip (page 1) retains the original BIOS image, and can
be used through manual configuration in the unlikely case where the primary BIOS
becomes corrupt.
If the primary BIOS becomes unbootable, use the secondary BIOS to manually boot
the blade server:
1. Log into the Shelf Manager.
2. To select the secondary BIOS image, type:
For example:
3. To boot the blade server from the Shelf Manager, type:
Note –
Once the blade server is booted, reset the blade server to use the primary
BIOS image (
page 0
).
# clia
sendcmd 96 2e 81 00 00 2a 01
# clia
sendcmd 96 2e 81 00 00 2a 01
<----- Setting the boot page to 1
Pigeon Point Shelf Manager Command Line Interpreter
Completion code: 0x0 (0) <----- successful completion code
Response data: 00 00 2A <----- no data returned
# clia
activate board
n
Summary of Contents for Sun Netra CP3250
Page 8: ...viii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 12: ...xii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 18: ...xviii Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 34: ...1 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 70: ...2 36 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 72: ...3 2 Sun Netra CP3250 Blade Server User s Guide April 2009 3 1 Block Diagram...
Page 80: ...3 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 94: ...5 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 96: ...A 2 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 1 BIOS Main Menu...
Page 97: ...Appendix A BIOS Screens A 3 FIGURE A 2 Advanced Configuration Menu...
Page 98: ...A 4 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 3 CPU Configuration Menu...
Page 99: ...Appendix A BIOS Screens A 5 FIGURE A 4 IDE Configuration Menu...
Page 100: ...A 6 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 5 USB Configuration Menu...
Page 101: ...Appendix A BIOS Screens A 7 FIGURE A 6 Event Log Control Menu...
Page 103: ...Appendix A BIOS Screens A 9 FIGURE A 8 Remote Access Configuration Menu...
Page 105: ...Appendix A BIOS Screens A 11 FIGURE A 10 Trusted Computing Menu...
Page 106: ...A 12 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 11 Boot Settings Menu...
Page 107: ...Appendix A BIOS Screens A 13 FIGURE A 12 Boot Device Priority Configuration Menu...
Page 108: ...A 14 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 13 Security Settings Menu...
Page 109: ...Appendix A BIOS Screens A 15 FIGURE A 14 Exit Menu...
Page 110: ...A 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Page 125: ...Appendix B Physical Characteristics B 15...
Page 126: ...B 16 Sun Netra CP3250 Blade Server User s Guide April 2009...