Power Supply Installation
2-9
2
Filter Cable
1. Free the filter cable.
a. On the inside of the power supply cage, cut the tie wrap and uncoil the
cable. See Figure 2-8.
b. Pass the cable connector through the rectangular hole in the power
supply cage and allow it to hang.
Figure 2-8
Freeing the Filter Cable
2.5.2.2 Power Supply Physical Installation
1. Install the springfingers, Part No. 340-2415-xx (two each — included with
the kit) on the new power supply.
Install each springfinger (shown in Figure 2-9) using three screws.
2. Place the supply on the power supply shelf at a slight angle so the left-
edge enters the power supply cavity first.
Filter cable
Tie wrap
Rectangular hole (hidden)