Sun SPARC Enterprise T5120 and T5220 Servers Service Manual • July 2009
FIGURE:
Removing FB-DIMMs
6. Press the Fault Locator button on the motherboard to identify the FB-DIMMs
that need to be replaced.
Tip –
Make a note of the faulty FB-DIMM location.
Note –
For memory configuration information, see
“FB-DIMM Configuration
Guidelines” on page 95
.
7. Push down on the ejector tabs on each side of the FB-DIMM until the
FB-DIMM is released.See
FIGURE: Removing FB-DIMMs on page 86
.
See panel 3 in the preceding figure.
Caution –
FB-DIMMs and heat sinks on the motherboard may be hot.
8. Grasp the top corners of the faulty FB-DIMM and lift it out of its slot.