E/0618/35A/47
7.2
Hydraulic connections
Make sure the condensate drain pipes do not interfere with the air flow.
Connections are carried out by the installer.
h > 0 mm
Use PVC pipes with an internal diameter of 14 mm
Connect the pipes to the plastic union at the rear of the conditioner
Make sure there is a slope of at least 2% towards the drain outlet
7.3
Electrical Connections
It is absolutely necessary, before making any connections, to use a suitable tester
to check the supply voltage. This must be the same as the voltage indicated on the
technical data plate.
The user must furnish and install, upstream from the unit, an isolating switch with
pre-fuse and capacity as specified on the technical plate in order to be able to
perform maintenance on the unit in the absence of electricity.
The ON/OFF-key on the C2020 keypad (if present) is only used for the unit stand-by.
It must therefore not be considered as a safety element to perform maintenance on
the unit. Maintenance must be done after disconnecting the power supply of the
unit (see note above).
Electrical connections may only be performed by authorised technicians.
The system must be connected to an efficient earth circuit.
The conditioning system must be electrically connected in compliance with the regulations at
paragraph 1.2 and national regulations for technical systems.
Check the supply voltage and frequency.
Check that supply voltage and frequency are compatible with those for the unit
(shown in its name-plate).
Interrupt both main power and auxiliary power before working on the system.
Summary of Contents for Tel-Air-2 Series
Page 2: ......
Page 27: ...E 0618 35A 27 TLD F 40 TLD F 60 TLD F 80 TLD F 40 TLD F 80...
Page 28: ...E 0618 35A 28 TLD F 90 TLD F A2 TLD F A4 TLD F 90 TLD F A4...
Page 29: ...E 0618 35A 29...
Page 30: ...E 0618 35A 30...
Page 31: ...E 0618 35A 31...
Page 37: ...E 0618 35A 37 Cut out TLF TLD 40 60 EXTERNAL OUTSIDE...
Page 38: ...E 0618 35A 38 Cut out FLOOR TLD 40 60 FRONT SIDE REAR SIDE...
Page 39: ...E 0618 35A 39 Cut out TLU 40 60 EXTERNAL OUTSIDE...
Page 40: ...E 0618 35A 40 Cut out TLF TLD 80 A4 EXTERNAL OUTSIDE...
Page 41: ...E 0618 35A 41 Cut out FLOOR TLD 80 A4 FRONT SIDE REAR SIDE...
Page 42: ...E 0618 35A 42 Cut out TLU 80 A4 EXTERNAL OUTSIDE...
Page 61: ...E 0618 35A 61...
Page 62: ...E 0618 35A 62...
Page 63: ...E 0618 35A 63...
Page 64: ...E 0618 35A 64...
Page 72: ......