Mechanical parts
Structure
These machines are built using self-supporting panels made of painted galvanised sheet metal to
guarantee good corrosion resistance (not suitable for corrosive and saline environments). They
make the machine easy to inspect and, at the same time, offer adequate protection to its internal
components. The external panels are internally lined with a 3 mm layer of sound-absorbing
material.
The internal components of the unit can be accessed by simply removing the cladding panels.
This is done by undoing their fastening screws.
Air filter
Belonging to class G4, it is designed to prevent large dirt particles present in the environment
from obstructing airflow through the evaporator.
Drip-tray
Made of sheet aluminium, it is located under the evaporator coil to collect the moisture from the
internal air which condenses on the surface of the coil during cooling. It is fitted with a union for
external drainage.
Damper
This damper, fitted in units featuring the free-cooling option, consists of a metal baffle powered
by a servomotor for directing inside and outside air flows. The damper body is made of
galvanised sheet metal.
3.4
Cooling components
The unit comprises a hermetic cooling circuit consisting of a compressor, condenser, refrigerant
filter, thermostatic valve and evaporator. The air inside the shelter is cooled without coming into
contact with the external air in cooling mode.
The system works as follows:
The compressor compresses the refrigerant gas bringing it to a high pressure and temperature.
The hot gas, by going through the condenser, is cooled and liquefied thus releasing heat to the
air in the environment. Pushed through the thermal expansion valve, the liquid refrigerant loses
pressure, which makes it prone to evaporation. This takes place in the evaporator, where the
refrigerant absorbs the heat of the warm air from the shelter, which is therefore cooled.
The circuit components are connected together by copper piping, appropriately welded to ensure
a greater seal. Schrader service valves are fitted internally on the compressor intake and return
lines.
Refrigerant
The refrigerant that is used is R407C (HFC). Optional: R134a.
Summary of Contents for Tel-Air-2 Series
Page 2: ......
Page 27: ...E 0618 35A 27 TLD F 40 TLD F 60 TLD F 80 TLD F 40 TLD F 80...
Page 28: ...E 0618 35A 28 TLD F 90 TLD F A2 TLD F A4 TLD F 90 TLD F A4...
Page 29: ...E 0618 35A 29...
Page 30: ...E 0618 35A 30...
Page 31: ...E 0618 35A 31...
Page 37: ...E 0618 35A 37 Cut out TLF TLD 40 60 EXTERNAL OUTSIDE...
Page 38: ...E 0618 35A 38 Cut out FLOOR TLD 40 60 FRONT SIDE REAR SIDE...
Page 39: ...E 0618 35A 39 Cut out TLU 40 60 EXTERNAL OUTSIDE...
Page 40: ...E 0618 35A 40 Cut out TLF TLD 80 A4 EXTERNAL OUTSIDE...
Page 41: ...E 0618 35A 41 Cut out FLOOR TLD 80 A4 FRONT SIDE REAR SIDE...
Page 42: ...E 0618 35A 42 Cut out TLU 80 A4 EXTERNAL OUTSIDE...
Page 61: ...E 0618 35A 61...
Page 62: ...E 0618 35A 62...
Page 63: ...E 0618 35A 63...
Page 64: ...E 0618 35A 64...
Page 72: ......