E/0618/35A/69
Optional auxiliary relay #2
Phase rotation check
DIP switch number
DIP switch number
15
Settin
16
Setting
OFF
Normal
OFF
Enabled
ON
Up-to-speed
ON
Disabled
12.10
Soft start for single-phase compressor
– SOFTM
Hazardous voltage: will cause death or serious injury. Disconnect power before
working on equipment.
Soft Start option is not available for TLx40 with single phase power supply and
refrigerant R407C.
In TLx60 units with 230V/1ph/50Hz power supply and refrigerant R407C is not
possible to add other options with Soft Start.
The Soft Start option is available for single phase power supply units up to TLx90,
in the units with refrigerant R134a. In TLx40/60 units with 230V/1ph/50Hz power
supply and refrigerant R134a is not possible to add other options with Soft Start.
To verify the availability of SOFTM option with 230V/1ph/60Hz power supply, please
contact your local partner STULZ.
Setting of this component is made in factory and must not be altered.
With SOFTM option, the working limit of the unit is 45°C external temperature.
The soft start is installed inside the e-box on the supply line to the compressor. Its purpose is the
reduction of compressor starting current and torque.
Technical data
Power supply
230 V AC +10% / -15% / 50/60Hz
Nominal operating current
25A / 32A max. / AC-53a; AC-58a
Protection class according to IEC 529
IP 20
Summary of Contents for Tel-Air-2 Series
Page 2: ......
Page 27: ...E 0618 35A 27 TLD F 40 TLD F 60 TLD F 80 TLD F 40 TLD F 80...
Page 28: ...E 0618 35A 28 TLD F 90 TLD F A2 TLD F A4 TLD F 90 TLD F A4...
Page 29: ...E 0618 35A 29...
Page 30: ...E 0618 35A 30...
Page 31: ...E 0618 35A 31...
Page 37: ...E 0618 35A 37 Cut out TLF TLD 40 60 EXTERNAL OUTSIDE...
Page 38: ...E 0618 35A 38 Cut out FLOOR TLD 40 60 FRONT SIDE REAR SIDE...
Page 39: ...E 0618 35A 39 Cut out TLU 40 60 EXTERNAL OUTSIDE...
Page 40: ...E 0618 35A 40 Cut out TLF TLD 80 A4 EXTERNAL OUTSIDE...
Page 41: ...E 0618 35A 41 Cut out FLOOR TLD 80 A4 FRONT SIDE REAR SIDE...
Page 42: ...E 0618 35A 42 Cut out TLU 80 A4 EXTERNAL OUTSIDE...
Page 61: ...E 0618 35A 61...
Page 62: ...E 0618 35A 62...
Page 63: ...E 0618 35A 63...
Page 64: ...E 0618 35A 64...
Page 72: ......