• According to the compressor manufacturer specifications the following parameters must be set depending
on the chiller unit type (stated in the table).
- RT
min
: minimum runtime of compressor
Command:
- Pause: minimum idle time of compressor
Command:
- CT
min
: minimum cycle time of compressor
Command:
min runtime
min idle time
min cycle time
on
off
Compressor operation
comp 1 minruntime 300
comp 1 pause 300
comp 1 mincycle 900
unit types
Rt
min
Pause
Ct
min
E_O 3002 to E_O 5102
s
300
300
600
E_O 6002 to E_O 14102
s
300
300
900