The connection piping should consist of P235 or a similar steel, like the water piping in the chiller, to avoid the
risk of corrosion at the transition to the external piping.
The connection is carried out in the shape of Victaulic connections. We recommend to insulate the pipes of
the external system, if they get in contact with external air, to prevent the introduction of heat from the ambient
air as well as possible.
• Remove the protective hoods from the water pipes.
• Connect the external piping to the chilled water lines of the chiller free of mechanical stress.
NOtICE
The hot gas lines are made of V2A stainless steel and are not isolated.
• Make sure that the tubes are not exposed to flying sparks when working with an ang
-
le grinder as this leads later to corrosion on the stainless steel tubes.