12
3.1.2
F
LOW
T
EMPERATURE OF
45
C
Frame
1
2
Model
30
35
40
45
50
U.M.
Power supply
400 -3N- 50
400 -3N- 50
400 -3N- 50
400 -3N- 50
400 -3N- 50
V-ph-Hz
IP
Heating A7W45
(Source: Air in 7°C d.b. 6°C w.b. / Plant: Water in 40°C out 45°C)
Heating capacity
29.6
34.8
39.1
44.6
51.0
kW
Power input
8.07
9.54
10.7
12.2
14.0
kW
COP
3.67
3.65
3.65
3.66
3.64
-
Water flow rate plant side
5127
6013
6761
7716
8811
l/h
Pressure drops plant side
22
29
36
32
41
kPa
Heating A2W45
(Source: Air in 2°C d.b. 1°C w.b. / Plant: Water in 40°C out 45°C)
Heating capacity
25.1
29.5
33.1
37.8
43.2
kW
Power input
8.06
9.52
10.6
12.2
14.0
kW
COP
3.11
3.10
3.12
3.10
3.09
-
Water flow rate plant side
4345
5109
5735
6552
7473
l/h
Pressure drops plant side
16
21
27
23
30
kPa
Heating A-4W45
(Source: Air in -4°C d.b. -5°C w.b. / Plant: Water in 40°C out 45°C)
Heating capacity
22.9
27.0
30.3
34.6
39.6
kW
Power input
8.08
9.53
10.7
12.2
14.0
kW
COP
2.83
2.83
2.83
2.84
2.83
-
Water flow rate plant side
3980
4675
5249
5996
6847
l/h
Pressure drop plant side
13
18
23
20
26
kPa
Heating A-7W45
(Source: Air in -7°C d.b. -8°C w.b. / Plant: Water in 40°C out 45°C)
Heating capacity
21.5
25.4
28.4
32.5
37.1
kW
Power input
8.08
9.54
10.7
12.2
13.9
kW
COP
2.66
2.66
2.65
2.66
2.67
-
Water flow rate plant side
3737
4397
4918
5631
6430
l/h
Pressure drops plant side
12
16
20
17
22
kPa
All data declared to
EN 14511
– the above values are referred to units without options or accessories.