17.7.2
O
PERATOR
S
ECTION
17.7.2.1 Parameters 20 & 30
No.
Operating line
Settings
20
Language
English, Deutsch, Français, Italiano, Nederlands, Español,
Português, Dansk, Suomi, Svenska, Polski, Słoweński,
Český, Slovenčina, Pyccknn, Magyar, Ελληνική, Türkçe,
Serbian,
Lietuvių
39
Commissioning menu
Off ¦ On
•
Language: Select language.
•
Commissioning Menu: Depending on the controller, the setting switches on or off the entire commissioning
wizard or just the chapter of the commissioning wizard specific to the operator unit.
Setting
Description
On*
The very first time a room unit or operator unit is commissioned, the
entire commissioning wizard or the supplemental chapter specific to the
operator unit is switched on.
The value is set to off after initial commissioning.
Off*
The entire commissioning wizard or the chapter specific to the operator
unit is switched off.
* Impact depends on controller
17.7.2.2 Parameter 40
– Used As
No.
Operating line
Settings
40
Used as
Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1
¦ Operator unit 2 ¦ Operator unit 3
•
Parameter 40
– It is preferably to set this parameter to “Operator Unit 1” as this controller will normally be
installed within the plant room therefore it will not be beneficial to use as a room controller.
17.7.2.3 Parameters 42 to 48
– Zone Assignment
No.
Operating line
Settings
42
Assignment device 1
Zone 1 ¦ Zone 1 and 2 ¦ Zone 1 and 3 ¦ All zones
44
Operation zone 2
Jointly with zone 1 ¦ Independently
46
Operation zone 3
Jointly with zone 1 ¦ Independently
47*
Room values device 1
Zone 1 only ¦ For all assigned zones
48
Warmer device 1
None ¦ Zone 1 only ¦ For all assigned zones
* Operating lines only available on QAA74
The following example illustrates applications available using the settings "Used as" (operating line 40) together
with "Zone assignment" (operating lines 42 to 48).
Examples
•
Parameter 40 – Set to Operator Unit.
•
Parameter 42 – Set to Zone 1, this will be addressed as the primary circuit between the heat pump and the
thermal store.
QAA74, unit 1
Operating line 40
Operator Unit 1
Operating line 42
Zone 1