MR0012J
9710 System Assurance Guide
A-5
Power usage for library without
drives
1
Watts 150 peak / 100 Continuous
KVA 0.15 Peak / 0.10 Continuous
Power usage for each 4890 drive
1
Watts 270 Peak / 230 Continuous
KVA 0.27 Peak / 0.23 Continuous
Power usage for each DLT drive
1
Watts 70 Peak / 60 Continuous
KVA .070 Peak / .060 Continuous
Heat output for library without
drives
680 BTU/hr
Heat output for each 4890 drive
880 BTU/hr
Heat output for each DLT drive
257 BTU/hr
Note:
1
Up to six drives take power from the 9710. Four additional drives take power from
the PDU box. Power ratings for the 9710, and (separately) for the PDU, are figured
by also adding the number of drives connected to each. The PDU box by itself has
zero load.
Table A-5. Power Characteristics (Continued)
Description
Value / Part Identification
Picture
Summary of Contents for 9710
Page 1: ...9710 Library Storage Module System Assurance Guide Document MR0012 ...
Page 2: ......
Page 3: ...9710 Library Storage Module System Assurance Guide ...
Page 12: ...Tables x 9710 System Assurance Guide MR0012J This page intentionally left blank ...
Page 18: ...Preface xvi 9710 System Assurance Guide MR0012J This page intentionally left blank ...
Page 35: ...MR0012J 9710 System Assurance Guide 3 7 Host Interfaces Figure 3 5 Host Indirect Connection ...
Page 52: ...SCSI Cabling 4 12 9710 System Assurance Guide MR0012J Figure 4 6 SCSI Connector Types ...
Page 80: ...A 6 9710 System Assurance Guide MR0012J This page intentionally left blank ...
Page 85: ......