INSTRUCTION MANUAL
GB
–
5/6
- DOC NO. BE0455020-A
-
After the detection distance learning operation, you should check that the VIGIBELT® CDM80 is in mode "1"
in normal operation and in mode "2" in the presence of a metal target (see LED status below).
-
Remove the adjustment tool and reposition the CDM80 on the opening, tighten the four M6 locknuts with
type L washers (clamping torque 4N.m) according to diagram E. Now it is put into operation.
Note: to make another adjustment, it is necessary to reset each detector by following the instructions
below, then resume steps 1 and 2 of the programming.
- Disassemble the CDM80 from the sheath to remove it from any metal mass.
- Press and hold the detector button, it turns off the green diode for 3 seconds, then it turns on for 4 seconds,
then turns off again. Release the button
- The detector is now without a resident program. You can resume the detection distance learning operation.
1_Normal operation:
GREEN DIODE ON AND ORANGE ON (contact closed)
2_Object in the detection field: GREEN DIODE ON AND ORANGE Off (open contact)
3_Electrical fault:
NO DIODE LIT
Led observation
window during sensor
setting
Return the access screw
to the learn button
Figure E
3s
4s
3
Flashes
=
RESET OK