INSTRUCTION MANUAL
GB
–
3/6
- DOC NO. BE0455020-A
- First assemble the M6 pan-head screws with the low nuts on the sheath (clamping torque 6N.m).
Connect the VIGIBELT® CDM80 according to the electrical diagram B or C:
NC detector = positive safety, permanent control of the correct functioning of the sensor
The loss of signal indicates that there is a problem with,
Belt misalignment
Electric wire cut
3-wire/NC connection scheme B
colours
BN = Brown
BU = Blue
BK = Black
PVC cable 2m for ATEX zone and not ATEX 3x0.34mm²
2-wire connection scheme C
colours
BN = Brown
BU = Blue
PVC cable 2m for non ATEX 2x0.34mm²
For low voltage sensor, ATEX or not
-
3-wire cable connection
-
L=2m cable
-
Voltage 12-24V DC
-
Voltage limits, including ripple, 10-36V DC
-
Switching power
≤
200 mA
-
temperature Operating: -25... 70°C (not ATEX)
-
temperature Operating: -20... 60°C (ATEX)
-
Protection - IP68
Caution: Any connection must be made outside the
ATEX zone
For multi-voltage sensor, out of ATEX zone
-
2-wire cable connection
-
L=2m cable
-
Voltage 24... 240V AC/DC
-
Voltage limits, ripple included 20... 264V AC/DC
-
Residual voltage at nominal I ≤5.5V
-
Switching power 5... 200 mA AC/DC
-
temperature Operating: -25... 70°C
-
Protection - IP68
It is imperative to put in series with the load a fast-
acting fuse of 0.4A
This pre-assembly easier the installation
of the VIGIBELT® CDM80