INSTRUCTION MANUAL
GB
–
4/6
- DOC NO. BE0455020-A
-
Define the detection range of VIGIBELT
®
CDM. To do this, first identify the
safety zone
that corresponds to the
minimum distance that the strap must never cross during a setback defect. Then identify the distance between
the edge of the strap and the edge of the metal target (Bucket or EAZY DETECT). These two values,
safety
zone
+
edge-to-edge distance
allow you to choose the detection range to program, i.e. 15, 20, 25, 30 or 35mm.
Sample application:
zone Security
= 10mm +
distense from board to edge
= 20mm; program the detection distance of the
VIGIBELT
®
CDM at 30mm
LEARN THE DISTANCE OF THE DETECTION TARGET:
DO NOT TURN OFF THE POWER DURING THIS OPERATION
-
Remove and keep the access screw to the learn button
-
Position the adjustment element with the desired remote
background sheet on the sheath then put the sensor.
-
Press with a 4-sided screwdriver and hold down the button, this first
triggers the extinction of the green diode, and then about 3 seconds
after it turns on again
-
Release the button,
-
The green diode flashes 3 times to indicate that learning is in
progress. 2 possibilities are then available:
➢
The green diode remains on
: it indicates that the detector
has recorded the position of the object
correctly
and is ready
to work. Any object passing through its detection field at this
distance will be detected.
➢
The green diode flashes very
quickly: distance learning
has failed
.
The requested distance is outside the allowed
range or absence of object in front of the detector. Or the
power was cut off after learning about the environment.
Perform a RESET and resume from the learning phase.
figure D
Calibration tool
with distance
determine in
advance
Programmable detection range
from 15 to 35
Learn button access screw
=
3 Flashes
3s
Finite learning
Fast
Flashe
s
=
3 Flashes
3s
Learning failed