17 West St., W. Hatfi eld, MA 01088
|
800.582.8423
|
413.247.3380
|
fax 413.247.3369
|
|
www.stiebel-eltron-usa.com
Simply the Best
INSTALLATION INSTRUCTIONS
SOL 27 PREMIUM S & W COLLECTORS - 230016 & 230017
Table of Contents
1 Safety
instructions
2 Collector
basics
3 Assembly
instructions
3.1
Important
information
4 Installation
instructions
4.1 Planning & installation
5 Mounting
5.1 General mounting system information
6
System Startup
6.1 Pressure & Leak Test
6.2 Setting the Expansion Tank Pre-charge Pressure
6.3 Final Chargin & Venting
7 Mainenance & care
8 Warranty
Appendix
A Certifi cations
!
CAUTION: READ ALL INSTRUCTIONS BEFORE
INSTALLING THESE COLLECTORS.
ADDITIONAL
ITEMS WILL BE NEEDED TO MOUNT THIS ASSEMBLY.
1 Safety
Instructions
General Information
Read this entire manual. Failure to follow all the guides,
instructions and rules could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service and use of this unit can result in serious
injury. This unit must be installed by a professional installer.
The installation must comply with all national, state and
local plumbing and electric codes. Proper installation is the
responsibility of the installer. Failure to comply with the
installation and operating instructions or improper use voids
the warranty. Save these instructions for future reference.
Installers should leave these instructions with the consumer.
If you have any questions regarding the installation, use or
operation of this product, or need any additional manuals,
please call our technical service line at 800.582.8423.
Safety Instructions
!
COLLECTOR WARNING: A SOLAR COLLECTOR
GENERATED HEAT FROM SUNLIGHT. THIS LEADS
TO THE COLLECTORS AND THEIR CONNECTORS GETTING
VERY HOT, EVEN WHEN THEY ARE NOT FILLED. COVER
THE COLLECTORS WITH OPAQUE MATERIAL UNTIL THE
INSTALLATION HAS BEEN COMPLETED.
!
SAFETY VALVE WARNING: NEVER INSTALL ANY
VALVES OR SHUT-OFF DEVICES IN THE PIPING
BETWEEN THE COLLECTORS AND THE SAFETY VALVE. THE
SAFETY VALVE IS ACTIVATED AT 87 PSI.
NEVER SET THE SOLAR LOOP PRESSURE GREATER THAN
THE DHW WATER SUPPLY PRESSURE. IF THE POTABLE
WATER PRESSURE IS TOO LOW, A BOOSTER PUMP MAY
BE NEEDED TO ASSURE THAT IT EXCEEDS THE REQUIRED
SOLAR LOOP PRESSURE.
The solar system must not bypass auxiliary system safety
devices.
Check Valve
The Flowstar pump station is equipped with two check
valves to prevent heat loss from single pipe thermo-
siphoning between the storage tanks and the solar loop and
collectors.
Drain Valve
Install a drain valve at the lowest point of the system.
Expansion Tanks
The diaphragm-type expansion tanks are designed for
an operating pressure of 87 psi and are resistant to
deterioration from propylene glycol mixtures.