background image

  7.  Check thermostat and replace if  
   defective.
  8.  Be sure 115 volts is supplied to the  
   

transformer primary, then check for 

   

24 volts at secondary terminal before  

   replacing.
  9.  Check and tighten all wiring connec- 
 

  tions per diagrams.

 10.  Replace, if necessary. Also see W, X  
  

symptoms.

  1.  Refer to “Installation, Venting”.

  1.  Relocate thermostat away from drafts.
 2. Replace 

thermostat.

  3.  Check wiring per diagrams.

  4.  Check operation at valve. Look for  
   

short (such as staples piercing  

   

thermostat wiring), and correct.

  5.  Replace gas valve.
  6.  Refer to “Operation”.

  1.  Tighten all electrical connections.

  2.  Adjust thermostat heat anticipator for  
   

longer cycles. Refer to “Operation”.

  3.  Check for proper air supply across 
   heat 

exchanger.

  4.  Relocate thermostat. (Do not mount  
   

thermostat on unit).

  5.  Eliminate drafts. Refer to Installation.
 6. Replace 

ignitor.

  7.  Check for proper air supply across 
   heat 

exchanger.

  8.  Jumper limit switch terminals 1 and 2.  
   

If burner operates normally, replace  

   switch.

  1.  Replace or tighten.
  2.  Clean fan wheel.
  3.  Replace vibration isolators.
  4.  Oil bearings on fan motor. (Refer to 
   

 label on motor).

  1.  Open all manual gas valves.
  2.  Increase size of pilot 

fl

 ame. Refer to  

  

“Operation”.

  3.  Purge air from gas supply.
  4.  Follow lighting instruction label  
 

  adjacent to gas valve.

  5.  Remove pilot ori

fi

 ce. Clean with  

 

  compressed air or solvent. (Do not  

  

ream).

  6.  Refer to “Operation”.
  7.  Check thermocouple connection,  
 

  and replace if defective.

  8.  Eliminate drafts. Refer to 

    

  

“Installation”.

  9.  Inspect and correct all wiring.
 10.  Inspect and correct ignition system  
 

  wiring. See symptoms W, X, & Y.

 11.  Replace.

23

Power Vented Propellers Troubleshooting Guide 

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

 7. Defective 

thermostat.

 8. Defective 

transformer.

 9. Loose 

wiring.

 10.  Defective ignition control.

 1. Improper 

venting.

  1.  Poor thermostat location.
 2. Defective 

thermostat.

  3.  Improper thermostat or transformer  
   

wiring at gas valve.

 4. Short 

circuit.

  5.  Defective or sticking gas valve.
  6.  Excessive gas supply pressure.

  1.  Loose electrical connections at gas  
   

valve or thermostat.

  2.  Excessive thermostat heat anticipator.

  3.  Unit cycling on high limit.

  4.  Poor thermostat location.

  5.  Draft on Pilot.
  6.  Defective ignitor control (if applicable).
  7.  Unit cycling on high limit.

  8.  Defective high limit switch.

  1.  Fan blades loose.
  2.  Fan blades dirty.
  3.  Vibration isolators deteriorated.
  4.  Bearings are dry.

  1.  Main gas off.
  2.  Pilot adjustment screw turned too low  
   

on combination/automatic main gas  

   valve.
  3.  Air in gas line.
  4.  Incorrect lighting procedure.

  5.  Dirt in pilot ori

fi

 ce.

  6.  Extremely high or low gas pressure.
 7. Defective 

thermocouple.

  8.  Drafts around unit.

  9.  Pilot valve not opening (faulty wiring).
 10.  No spark (faulty wiring).

  11.  Defective gas valve.
  

 

J.  Condensation of water vapor.

 

K.  Burner won't turn off.

  L.  Rapid burner cycling.

  M.  Noisy.

  N.  Pilot will not light or will not      
   stay 

lit.

 

H.  Failure to ignite.

Summary of Contents for QVSF 100

Page 1: ...aks or loose fasteners may occur It is the installer s responsibility to inspect and correct any problems that may be found RECEIVING INSTRUCTIONS Inspect shipment immediately when received to determi...

Page 2: ...ardous situation which if not avoided may result in minor injury or property damage NOTICE Used to notify of special instructions on installation operation or maintenance which are important to equipm...

Page 3: ...in accordance with local codes or in absence of local codes with the latest edition of ANSI Standard Z223 1 N F P A No 54 National Fuel Gas Code All of the ANSI and NFPA Standards referred to in thes...

Page 4: ...C Hanging Distance Width 14 3 4 17 1 2 17 1 2 20 1 4 23 25 3 4 28 1 2 34 39 1 2 45 375 445 445 514 584 654 724 864 1003 1143 D Discharge Opening Width 15 3 8 18 1 8 18 1 8 20 7 8 23 5 8 26 3 8 29 1 8...

Page 5: ...e to the enforcing authorities PUBLIC GARAGES In repair garages unit heaters must be at least 8 feet 2 4m above the floor Refer to the latest edition of NFPA No 88B Repair Garages In parking structure...

Page 6: ...es 635mm is required The distance between the flue collector and any combustible must be no less than 6 inches 152mm Also see COMBUSTION AIR and EXHAUST VENTING sections NOTICE Increasing the clearanc...

Page 7: ...S Multiply the Cu Ft Hr value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid equipment damage...

Page 8: ...14 in W C 3 5 kPa All piping should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CAN CGA B149 See Tables 1 and 3 for correct gas...

Page 9: ...ndard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energizing the unit heater electr...

Page 10: ...10 Figure 6...

Page 11: ...11 Figure 7...

Page 12: ...12 Figure 8...

Page 13: ...13 FIGURE 9...

Page 14: ...ertical combustion air pipes should be piped as depicted in Figure 10 7 The equivalent length of the vent system must not be less than 5 feet and must not exceed 50 feet 15 2m Equivalent length equals...

Page 15: ...f the vent system that passes through a combustible material must be properly insulated Figure 10 Vertical Intake Vent Installation NOTICE Increasing the clearance distances may be necessary if there...

Page 16: ...16 Figure 10A Horizontal Intake Vent Locations Figure 11 Vertical Vent Installation Figure 11A Horizontal Vent Installation...

Page 17: ...t operates the vent and ignition systems to control the temperature of the space being heated NOTICE The thermostat must be mounted on a vertical vibration free surface free from air currents and in a...

Page 18: ...TO UNIT WIRING DIAGRAM 8A MAIN GAS VALVE HONEYWELL 8B MAIN GAS VALVE WHITE RODGERS 9 HONEYWELL IGNITOR 10 HONEYWELL PILOT BURNER 12 FAN TIME DELAY SWITCH 13 HI LIMIT LOCATED ON REAR HEADER PLATE OF H...

Page 19: ...of 2000 ft 610m or less SPECIAL ORIFICES ARE REQUIRED FOR INSTALLATIONS ABOVE 2 000 FT 610M When installed in Canada any references to deration at altitudes in excess of 2000 feet 610m are to be igno...

Page 20: ...ical power to the gas unit heater 3 To clean or replace the main burners remove the bottom panel and compress the spring by moving the burner toward the manifold Slide the opposite end of the burner d...

Page 21: ...URE SWITCH POWER VENT ASSY POWER VENT MOTOR FAN MOTOR GAS SUPPLY INLET AIR INLET FAN GUARD GAS VALVE RETAINER SPRING AIR SHUTTERS PILOT ASSY MANIFOLD Figure 15 Internal Furnace Assembly MAIN BURNERS F...

Page 22: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Page 23: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition syst...

Page 24: ...for short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check moto...

Page 25: ...lve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltage...

Page 26: ...no adapter required 300 400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 26 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter...

Page 27: ...en instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any da...

Page 28: ...nless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Check damper li...

Reviews: