20
MAINTENANCE
PERIODIC SERVICE
NOTICE: The heater and vent system should be
checked once a year by a qualifi ed technician.
All Maintenance/Service information should be recorded
accordingly on the Inspection Sheet provided in this
manual.
Open all disconnect switches
and disconnect all electrical and gas supplies
and secure in that position before servicing unit.
Failure to do so may result in personal injury or
death from electrical shock.
Gas tightness of the safety shut-
off valves must be checked on at least an annual
basis.
To check gas tightness of the safety shut-off valves,
turn off the manual valve upstream of the appliance
combination control. Remove the 1/8 inch pipe plug on
the inlet side of the combination control and connect
a manometer to that tapping. Turn the manual valve
on to apply pressure to the combination control. Note
the pressure reading on the manometer, then turn the
valve off. A loss of pressure indicates a leak. If a leak
is detected, use a soap solution to check all threaded
connections. If no leak is found, combination control is
faulty and must be replaced before putting appliance
back in service.
Should maintenance be required, perform the following
inspection and service routine:
1. Inspect the area near the unit to be sure that there is
no combustible material located within the minimum
clearance requirements listed in this manual.
Under no circumstances should
combustible material be located within the
clearances specified in this manual. Failure to
provide proper clearance could result in personal
injury or equipment damage from fi re.
2. Turn off the manual gas valve and electrical power
to the gas unit heater.
3. To clean or replace the main burners, remove the
bottom panel and compress the spring by moving
the burner toward the manifold. Slide the opposite
end of the burner downward from the locating slot
while retaining spring is still compressed. Pull the
burners away from the heat.
4. With the burners removed, wire brush the inside
surfaces of the heat exchanger.
5. Remove any dirt, dust, or other foreign matter from
the burners using a wire brush and/or compressed
air. Ensure that all parts are unobstructed. Inspect
and clean pilot burner if necessary.
6. Reassemble the gas unit heater by replacing all
parts in reverse order.
7. Relight the pilot (see lighting instruction plate
on the unit). Complete the appropriate unit start-
up procedure as given in the “Operation” section of
this manual.
8. Check the burner adjustment. See the “Primary
Air Shutter Adjustment” section of this manual.
9. Check all gas control valves and pipe connections
for leaks.
10. Check the operation of the automatic gas valve
by lowering the setting of the thermostat, stopping
the operation of the gas unit heater. The gas valve
should close tightly, completely extinguishing the
fl
ame on the main burners.
11. Inspect and service the motor/fan assemblies. To
maintain efficient air flow, inspect and clean the
fan blades and guard to prevent buildup of foreign
matter.
12. Check lubrication instructions on the motor. If oiling
is required, add 3 to 4 drops of electric motor oil as
follows:
(a.) Light Duty - After 3 years or 25,000 hours of
operation.
(b.) Average Duty - Annually after 3 years or 8,000
hours of operation.
(c.) Heavy Duty - Annually after 1 year or at least
every 1500 hours of operation.
Never over oil the motor or pre-
mature failure may occur!
13. Check and test the operational functions of all safety
devices supplied with your unit.
Summary of Contents for QVSF 100
Page 10: ...10 Figure 6...
Page 11: ...11 Figure 7...
Page 12: ...12 Figure 8...
Page 13: ...13 FIGURE 9...