background image

18

OPERATION

 Never operate the unit beyond the 

specified limits or severe damage to, and/or 
premature failure of, the unit will result!

EXPLANATION OF CONTROLS
1.  Each Separated Combustion Duct Furnace comes 

equipped with a power vent system that consists of a 
power ventor motor and blower, pressure switch, and 
sealed fl ue collector.  (See Figure 15)

 The addition of external draft hoods 

or power ventors is not permitted. Addition of such 
devices may cause serious unit malfunction or 
failure.

2.  The power ventor is energized by the room thermostat 

when a demand for heat is sensed. The pressure 
switch measures the differential pressure between 
the air inlet and the exhaust vent systems. If the 
differential is correct, the indirect spark ignition 
system is energized.

 Under no circumstances is the 

unit to be fi red if the power ventor is not operable, 
or severe personal injury or death may occur!

3.  The indirect spark ignition system consists of an 

ignition module, a dual combination gas valve, and a 
spark-ignited pilot burner. When the pressure switch 
is closed, the pilot valve opens as a spark is generated 
to light the pilot. When the fl ame is sensed by the 
fl ame sensing circuit, the spark ceases, and the main 
gas valve opens to supply gas to the main burners.  
Once the thermostat is satisfi ed, the vent system and 
gas valve are simultaneously de-energized, stopping 
all gas fl ow to the unit.

4.  The high limit switch interrupts the fl ow of electrical 

current to the main gas valve if the duct furnace 
becomes overheated.

5.  The optional fan switch delays the operation of the 

fan for approximately 45 seconds once the thermostat 
is closed, and continues fan operation for 
approximately 65 seconds after the thermostat opens. 
The start-up fan delay must not exceed 90 seconds 
from a cold start.

6.  The wall thermostat, supplied optionally, is a 

temperature sensitive switch that operates the vent 
and ignition systems to control the temperature of 
the space being heated.

NOTICE: The thermostat must be mounted on a 
vertical, vibration-free surface, free from air currents, 
and in accordance with the furnished instructions.

INITIAL LIGHTING
1.  Open the manual gas valve, in the gas supply line to 

the duct furnace.  Loosen the union in the gas supply 
line to purge it of air. Tighten the union, and check for 
leaks.

NOTICE: Check all pipe joints for leakage using a soap 
solution or other approved method. 

 Never use an open fl ame to detect 

gas leaks. Explosive conditions may exist which 
could result in property damage, personal injury 
or death.

 Before attempting to light or 

relight the pilot, wait 5 minutes to allow gas 
which may have accumulated in the burner 
compartment to escape. Failure to heed this 
warning could result in property damage, 
personal injury or death!

2.  Turn on electrical power. The duct furnace should now 

be under the control of the thermostat.  Set the 
thermostat to it's highest setting, the power ventor 
motor should start, and burner ignition occur. Turn 
the thermostat to the lowest setting. The burners and 
power ventor should stop operating immediately.  
Reset the thermostat to the desired operational 
setting.

PRIMARY AIR SHUTTER ADJUSTMENT
After the unit has been operating for at least 15 minutes, 
adjust the primary air flow to the burners. Turn the      
friction-locked, manually-rotated air shutters clockwise to 
close, and counterclockwise to open.

For correct air adjustment, close the shutter until yellow 
tips in the fl ame appear.  Then, open the air shutter to the 
point just beyond where the yellow tipping disappears.  
Refer to Figure 12.

NOTICE: There may be momentary and spasmodic 
orange fl ashes in the fl ame. This is caused by the 
burning of airborne dust particles, and should not 
be confused with yellow tipping, which is a stable, or 
permanent, situation when there is insufficient 
primary air.

Figure 12 - Main Burner Flames

SHUT DOWN
1.  Turn the valve selector knob to the "OFF" position.
2.  Turn off the electricity.
3.  To relight, follow "Initial Lighting" instructions.

NORMAL

(HARD FLAME)

LIFTING

(TOO MUCH AIR)

YELLOW TIPPING

(MARGINAL)

YELLOW FLAME

(TOO LITTLE AIR)

Summary of Contents for QVSD-100

Page 1: ...e This equipment has been test fired and inspected It has been shipped free from defects from our factory However during shipment and installation problems such as loose wires leaks or loose fasteners...

Page 2: ...00 feet 610m above sea level derate the input by 4 for each 1 000 feet 305m rise above sea level Special orifices are required for installations above 2 000 feet When units are installed in Canada any...

Page 3: ...eral safety information may result in extensive property damage severe personal injury or death This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealt...

Page 4: ...664 603 645 127 103 225 28 7 8 26 1 2 28 1 8 5 3 4 1 2 or 3 4 246 733 673 714 127 116 250 31 5 8 29 1 4 30 7 8 5 3 4 1 2 or 3 4 266 803 743 784 127 121 300 37 1 8 34 3 4 36 3 8 6 3 4 1 2 or 3 4 305 94...

Page 5: ...7 0 873 50 0 02 3 930 11 0 48 250 250 125 200 2 056 90 0 09 9 251 20 1 96 73 2 36 6 58 6 0 970 50 0 02 4 366 11 0 49 300 300 150 240 2 467 90 0 10 11 101 20 2 00 87 8 43 9 70 3 1 164 50 0 02 5 240 11...

Page 6: ...nce purposes AIRCRAFT HANGARS Separated Combustion Duct Furnaces must be installed in aircraft hangars as follows Duct furnaces must be at least 10 feet 3 05m above the upper surface of wings or engin...

Page 7: ...ents AIR FLOW The installation is to be adjusted to obtain an air throughput within the range specified on the appliance rating plate Figure 2 Recommended Design for Field Installation of Ductwork for...

Page 8: ...res 6 and 7 THERMOSTAT WIRING AND LOCATION NOTICE The thermostat must be mounted on a vertical vibration free surface free from air currents and in accordance with the furnished instructions Mount the...

Page 9: ...9 Figure 6 Standard Wiring Diagram for Unit with Honeywell Ignition System...

Page 10: ...10 Figure 7 Standard Wiring Diagram for Unit with Johnson Ignition System...

Page 11: ...Use single wall pipe constructed of 26 gauge galvanized steel or material of equivalent durability and corrosion resistance for the combustion air system For installations in Canada use pipe construc...

Page 12: ...uivalent must be used to seal each joint General Electric RTV 108 Dow Corning RTV 732 or an equivalent may be used instead of the tape 9 For horizontal vent systems longer than 5 feet 1 5m the system...

Page 13: ...13 CAT 2766 CAT 2767 CAT 2765 Figure 8A Horizontal Intake Vent Locations Figure 9 Vertical Vent Installation Figure 9A Horizontal Vent Installation...

Page 14: ...ws 1 Find cu ft hr by using the following formula Input Cu ft hr BTU Cu ft 2 Refer to table 4 Match Length of Pipe in Feet with appropriate Gas Input Cu Ft Hr figure This figure can then be matched to...

Page 15: ...ce A ground joint union and a manual gas shutoff valve should be installed ahead of the unit heater controls to permit servicing The manual shutoff valve must be located external to the jacket See Fig...

Page 16: ...Intermittent Pilot Ignition BURNER DRAWER COMMON PARTS 1 MAIN BURNERS 2 BURNER MANIFOLD 3 AIR SHUTTERS 4 BURNER SPRINGS 5 MAIN BURNER ORIFICE 6 TRANSFORMER 7 PILOT TUBING CONTROLS 8A MAIN GAS VALVE HO...

Page 17: ...RILL GAS INPUT RATE Never overfire the duct furnace as this may cause unsatisfactory operation or shorten the life of the heater Check the gas input rate as follows Refer to General Safety Information...

Page 18: ...rature of the space being heated NOTICE The thermostat must be mounted on a vertical vibration free surface free from air currents and in accordance with the furnished instructions INITIAL LIGHTING 1...

Page 19: ...pplied with your unit MAINTENANCE PERIODIC SERVICE Open all disconnect switches and secure in that position before servicing unit Failure to do so may result in personal injury or death from electrica...

Page 20: ...18 Tubing Aluminum Formation 19 Male Connector 20 Locknut 21 Hole Plug 22 Pressure Switch Cover 23 Drill Screw 24 Junction Box Base 25 Relay Purge NOTES 1 For item No 6 use counter clockwise rotation...

Page 21: ...ice size and replace Refer to Operation 1 Close air shutter 2 Reduce pilot gas Refer to Operation 3 Replace orifice 4 Reset manifold pressure Refer to Operation Replace regulator section of combinatio...

Page 22: ...hermostat 3 Check wiring diagrams 4 Check operation at valve Look for short such as staples piercing thermostat wiring and correct 5 Replace gas valve 6 Refer to Operation Table 7 Troubleshooting Guid...

Page 23: ...onnections 2 Adjust thermostat for longer cycles Refer to Operation 3 Check for proper air supply across heat exchanger 4 Relocate thermostat do not mount thermostat on unit 5 Eliminate drafts Refer t...

Page 24: ...ay is defective and must be replaced If 24V in not present check wiring per wiring diagrams 1 Be sure ventor relay heater terminals are connected per diagrams 2 Replace ventor motor 3 Check motor amps...

Page 25: ...k motor voltage with fan running Should be 115 volts AC 3 Refer to Operation 1 Close thermostat contacts 2 Check for 24V across 24V terminals of S8600 3 Set gap to 0 1 4 Replace pilot assembly 1 Check...

Page 26: ...val or reinstallation of the Product c to any damage due to corrosion by chemicals including halogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 Thi...

Page 27: ...27...

Page 28: ...equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Chec...

Reviews: