Sterling Power Pro Batt Ultra BB122470 User Manual Download Page 9

Sterling Power Products

Copyright 

On  first  start  up  all  LEDs  will  light  up. A  beep  should 
sound.  The  fan  shall  then  start  running  for  around  5 
seconds. If, after this, 2 red LEDs flash for 8 seconds 
you may have a calibration issue and the unit should be 
returned to Sterling. If 2 solid red LEDs are on at the top 
or bottom then you either have high or low input voltage 
(respectively) - check your voltages.

Changing charging profile during startup

After the initial start up an LED on the left panel shall 
light up for 5 seconds, this shall indicate the battery type 
selected  - 

default  is  sealed  lead  acid

.  This  is  your 

window of opportunity to change the charging profile. If 
you have missed the opportunity, you can wait for the 
unit  to  go  in  to  normal  operation  and  follow  the 
instructions on the right of the page or restart the device.

Hold  down  both  buttons  on  the  front  panel  (SELECT 
and  SETUP/ENTER)  for  more  than  10  seconds  (less 
than 20 seconds!). All LEDs on the left column shall now 
flash.  By  using  these  two  buttons  toggle  through  the 
various profiles (see below). The right button is up the 
column and the left button takes you down the column. 
The LED shall light up demonstrating which profile you 
have selected. When the LED has illuminated at your 
desired profile simply hold both buttons for a couple of 
seconds or simply just leave the charger alone for 30 
seconds  and  it  will  change.  The  chosen  profile  LED 
shall  then  flash.  The  unit  shall  then  restart  and  go 
through the starting cycle again. 

Note

 - if you can only see LEDs on the right column the 

chances are you are in an error mode. This could be 
down  to:  Very  low  output  voltages  (<5V),  no  output 
connection,  reverse  polarity  or  the  device  is  not 
detecting  a  valid  operational  mode  as  the  connector 
wire  is  either  not  connected  or  the  connection 
configuration is wrong. Please refer to previous page. 

Left and right meter readings.

During normal operation

Out of range voltage values

If  voltage  exceeds  the  meter’s  range  the  upper  right 
LED shall flash. If the voltage falls short of the meter’s 
range  the  lower  LED  shall  flash.  If  two  neighbouring 
LEDs, on the voltmeter, are on simultaneously then the 
real  voltage  is  between  these  two  parameters. 
Example, if LEDs at 14.6V and 14.2V were on then the 
approximate voltage shall be ~14.4V.

Low or high output voltages

If the output voltage is below 1V (2V at 24V) or reverse 
polarity  then  the  low  output  voltage  LED  will  flash 
(number 23). Similarly, if the output voltage is above 
15.5V (31.0V at 24V) the high voltage LED shall flash 
(number  16).  To  resurrect  these  problems,  bring  the 
voltage  above  1V  on  the  output  and  below  15.5V, 
correct the polarity and then restart the device. 

Return  to  factory  default: 

This  shall  irreversibly 

erase all previously entered settings

. Press and hold 

both  buttons  for  30    and  let  go.  The  LED 
columns  shall  alternatively  flash.  To  confirm  factory 
default press BOTH buttons again for 2 seconds. Once 
confirmed,  3  green  LEDs  on  both  columns  shall  flash. 
Then, LEDs on the front panel shall light up in a clockwise 
pattern.  The  unit  should  then  reboot  with  the  default 
settings. To reject factory default settings, simply let the 
LED columns continue alternatively flashing. 

To view charger’s status:

Simply hold the SELECT button for 1 second and the right 
LED should flash indicating the status of the charger. This 
shall  flash  for  8  seconds.  To  return  quickly,  press  the 
SETUP/ENTER button once.

After unit has gone through its startup sequence the 
LEDs displayed should be the input voltage on the left 
column  and  the  output  voltage  on  the  right  column. 
Also, the top left LED (number 12) should be on solid 
which is the fast charge (bulk) LED. 

15.4 V
15.0 V
14.6 V
14.2 V
13.8 V
13.4 V
13.0 V
12.6 V
12.2 V

   Input voltage

    

   (x2 for 24V)

     Output voltage

              (x2 for 24V)

Bulk / Boost         Absorb             Cond.     Float (s) / Standby (fl)

IUOU

Battery charge
          progress

Charge state ->

Remember

 it is the voltages which are more important 

than our battery types. After installation test the voltage 
from the unit is the desired voltage. 

Ensure you remove 

at least 1 wire from the battery temperature sensor as 
the product voltage may be higher ( if in cold climate ) 
or lower ( if in warm climate ) than the preconceived 
voltage.

 

The  voltage  requirements  of  the  battery 

company will override our recommendations as it is them 
who are supporting the battery warranty.

Changing charging profile during operation.

While the unit is running, simply hold down the SETUP 
and SELECT buttons for 10-20 seconds and let go. The 
LEDs  on  the  left  column  shall  light  up.  The  procedure 
hereafter is the same as above. 

*Lithium  profile  has  reverse  polarity  protection 
disabled. **All voltages shall be 0.1V higher for the 
first 3 minutes of the chargers operation.

           Output V

oltage

15.4V
15.0V
14.6V
14.2V
13.8V
13.4V
13.0V
12.6V
12.2V

16
14
12
10

8
6
4
2
0

840
720
600
480
360
240
120

30

0

High Volt in (fl) / out (S)
High temp trip (fl)

No Fault (S) / P.Pack (fl)

Regen timer off (S) / on (fl)

Batt. Sense on (S)

Volt drop sense (fl)
1/2 power (S) / night (fl)  

Low Volt in (fl) / out (S)

                     
                     Bulk / Abs.    Cond.   Float     Min | Abs. | Max   

Volts
14.00
14.10
14.40
14.40
14.60
14.80
15.10
15.50
14.40
      Custom Charging Profile

Volts
13.70
13.40
13.60
13.80
13.70
13.30
13.60
--------
13.80

Mins

60
60

120
720

60
60
60

240

30

Mins

600
480
480

1440

480
480
360
240

30

Volts
13.85
13.75
14.15
14.00
14.10
14.00
14.30
--------
13.80

Options
1) Gel I
2) AGM I
3) Sealed
4) Gel II
5) AGM II
6) Open
7) Calcium
8) De-sulphation
9) LiFePO

4

10) Custom

 First Time Use (when wiring up)

If 

battery 

temperature 

sensor 

is 
connected 

then 

all 
voltages 

are 

based 

on 

20 

Deg 

C. 
If 

sensor 

senses less than 20DegC = increased voltage. 

Higher 

than 

20DegC 


decrease 

voltage. 

The 

further 

from 

20DegC 

in 
either 

direction 

leads 

to 

p

ro

p

o

rt

io

n

a

in

c

re

a

s

e

 

o

d

e

c

re

a

s

e

 

in

 

th

voltage.  

 (x2 

for 
24V 

| x3 
for 
36V 

| x4 
for 
48V)

High bat temp (fl) SVEM (S)

9

Summary of Contents for Pro Batt Ultra BB122470

Page 1: ...nsor USERS MANUAL Sterling Power Products H Charge Float In Unit Out Rem Batt V 12 2 Temp Menu Change Volts Select Audible alarm on off hold 3 sec On Off hold 3 sec Fault Absorption Cond Optional Remo...

Page 2: ...e Unit on off Display annotations Page 4 5 Force Unit to half pow er mode Front Label display annotated Sleep timer Off timer adjust Under the lid annotation Custom Battery Profile Selection Pages 11...

Page 3: ...rrent limiting With fuses protecting the DC cables In a well ventilated dry dust free and condensation free environment When instruction manual has been read through Safety Symbols Example WARNING Nev...

Page 4: ...r bottom red LED is on then the voltage is outside the parameters off the voltmeter 16 High voltage if on solid it is high output voltage if flashing it is high input voltage 10 11 13 8 9 7 6 5 4 3 12...

Page 5: ...ed Models BB1260 BB122470 BB123670 BB124870 BB242435 BB241235 Models BB1230 BB122440 Front Panel II 8 1 2 3 4 6 7 10 11 12 13 9 5 14 5 3 4 1 6 BB122470 BB123670 BB124870 BB1260 BB242435 BB241235 4 60...

Page 6: ...on default setting if temperature sensor not fitted Ignition Force mode For true ignition on off mode the Link should be removed As soon as there is a signal 4V on this connector the unit will wake u...

Page 7: ...UP SELECT to toggle between types Both to confirm 20 30 Change operational on off voltages use both buttons to scroll between voltages 30 Reset unit to default press and hold both buttons for 2 second...

Page 8: ...gger voltages only a 10V 20V at 24V low voltage trip With the link wire connected and the ignition feed connected the BB shall operate when the ignition is live However it shall also operate when ther...

Page 9: ...old both buttons for 30 seconds and let go The LED columns shall alternatively flash To confirm factory default press BOTH buttons again for 2 seconds Once confirmed 3 green LEDs on both columns shall...

Page 10: ...hen falls below 13 0V x2 for 24V the auto regen timer starts to count If the voltage does not rise above 13 2V the timer will not reset and the unit will switch off however as soon as the voltage rise...

Page 11: ...s ________ Absorption Maximum 0 960 minutes ________ STERLI G POWER Operation Press and hold both buttons for 10 20 seconds All Left LEDs shall flash Press the setup select button to move LED down to...

Page 12: ...ck mode constant voltage full current accessibility Stage 4 Backlash voltage If charger power exceeded and battery discharge unit resets to stage 1 Stage 5 Time Depending on battery size type state of...

Page 13: ...e display shall read loc on number you have stored To remove loc return to loc and re enter the number Press select button and the display should read loc off green back light Please make a note of th...

Page 14: ...ltage is 0 13V starter battery voltage then alternator may have failed Or requires increase rpm of engine possible belt slip Is your output voltage slightly higher or lower than expected even with no...

Page 15: ...does not apply for shipping organised by yourself Please do not throw out any shipping or packaging materials All returns for any reason will require a proof of purchase with the purchase date The pr...

Page 16: ...eitshinweise und allgemeinen Bedingungen Auch empfehlen wir Ihnen die Installation durch einen Fachbetrieb durchf hren zu lassen Bestell Nr BB1230 12V 12V 30A BB1260 12V 12V 60A BB122470 12V 24V 70A B...

Page 17: ...Deckel Techn Daten Emfpohlene Kabelst rken und Sicherungen Schnell Installationshilfe Seite 6 Standard Anschluss Skizze Basis Operations Modus Ausf hrliche Installationshilfe Seite 7 8 Installations D...

Page 18: ...n Sicherheits Symbole Beispiel WARNUNG Benutzen Sie das Produkt niemals in Umgebungen wo die M glichkeit einer Gas oder Staub Explosion besteht oder brennbare Produkte sind Generelle Wartung und Repar...

Page 19: ...len Batterietyps dienen die LEDs zur Anzeige des Wertes Status und Fehleranzeigen 16 berspannung Zu hohe Eingangsspannung blinken zu hohe Ausgangsspannung an 10 11 13 8 9 7 6 5 4 3 12 14 15 16 17 18 2...

Page 20: ...m 5m Empf Sicherung 30A Ger t 6mm 10mm 16mm 16mm 25mm 50A 60A Ger t 16mm 25mm 25mm 35mm 35mm 100A Technische Daten bei 24V x2 36V x3 48V x4 Max Eingangsspannung 20V Spannungs Arbeitsbereich 11 19V Aus...

Page 21: ...g entladen wird Automatische Aktivierung und bei Signal eingang mit tiefer Eingangsspannunsregelung Dieses ist eine Kombination der Modi 1 und 3 Automatik und zus tzlich bei Signaleingang bis zu 10V E...

Page 22: ...ES SIGNAL z B Z ndung 7 F r 24V alle Spannungen x 2 f r 36V alle Spannungen x3 und f r 48V alle Spannungen x4 Installationsanleitung 1 3 Direktaktivierung ber externes Signal und sehr tiefe Eingangssp...

Page 23: ...ngs und Ausgangskabel an den Kabelklemmen 5 3 an Achten Sie darauf dass die Kabel entsprechend abgesichert sind Nachdem beide Kabel angeschlossen sind verbinden Sie das Ausgangs Ladekabel mit dem Posi...

Page 24: ...en LEDs 16 24 Es gilt die gr ne Spannungsspalte Einstellung und Abschluss wie 8 10 8 13 Ausgleichsladungszeitfaktor ausw hlen Dieser Faktor bestimmt die berechnete Zeit der Aus gleichsladung Dabei wir...

Page 25: ...Enter Select Das Ger t kann hiermit in den Werk Auslieferzustand zur ckgesetzt werden Alle linken und rechten LEDs blinken abwechselnd Innerhalb von 10 Sekunden muss diese Aktion durch gleichzeitiges...

Page 26: ...ns nicht aktiv Nach 8 Std oder durch Standby oder im Schlafmo dus schaltet das Ger t automatisch wieder zur ck 9 13 Standby ein aus 5 Sekunden Select Durch Dr cken der Select Taste f r mehr als 5 Seku...

Page 27: ...chaltet worden Leuchtet die LED ist das Ger t entweder aktiv in den 1 2 Leistungsmodus geschaltet worden oder die Lei stung wurde aufgrund einer zu hohen Ger tetempe ratur 85 C reduziert In diesem Fal...

Page 28: ...annungen und Zeiten W hlen Sie dann den Batterietyp welcher den Empfehlungen am N chsten ist Aber immer von den Spannungen nach Unten am N chsten Z B empfiehlt der Hersteller 14 5V muss ein Batteriety...

Page 29: ...sGer tnichtimSchlafmodusist Wichtig Ist das Ger t mit der Fernbedienung ausgeschaltet worden geht es zwar in den Schlafmodus wenn die Eingangsspannung abf llt steigt die Spannung wieder an Motor wird...

Page 30: ...bLt Zeit der Hintergrundbeleuchtung 1 600 Sekunden 0 st ndig an Standard 60 br9 Farbwechsel Spannung von rot zu gr n 8 0 13 3V Standard 12 4V b9b Farbwechsel Spannung von gr n zu blau 12 4 16 0V Stand...

Page 31: ...Sicherungen funktionieren und nicht durchgebrannt sind Auch Korrosion kann erheblichen Einfluss auf den Stromfluss haben Ein und Ausschalten des Ger tes mit einer Pause von mindestens 10 Sekunden kom...

Reviews: