 Troubleshooting:

TROUBLESHOOTING GUIDE

Symptom

Possible Causes

Solutions

Pressure Drop

Sediment filter clogged

•  replace filter cartridge with appropriate 5 

micron cartridge

Note:

 check source water supply as fluctuations 

may occur in source pressure

High Bacteria 
Counts

Quartz sleeve is stained 

or dirty

•  clean sleeve with scale cleaner and eliminate 

source of staining problem (ie. soften hard 

water, see page 8)

Change in feed water  

quality

•  have source water tested to ensure that water 

quality is still within allowable limits for this 

system

Contamination in water 

lines after UV system

•  it is imperative that effluent water stream be 

shocked with chlorine (bleach) before water 

leaves UV system - disinfection system must 

have a bacterial free distribution system to 

work effectively (see page 6)

Possible break-through  

of sediment through 

pre-filter

•  have source water tested for turbidity - may 

need stepped filtration in order to catch all 

sediment entering water system (20 micron 

filter followed by a 5 micron filter followed by 

UV system)

Heated 
Product Water

Common problem 

caused by infrequent  

use of water

•  run water until it return to ambient 

temperature

•  install temperature management valve

Water Appears 
Milky

Caused by air in the  

water lines

•  run water until air is purged

Chamber
Leaking Water

Problem with o-ring  

seal (on gland nut     

and/or UV sensor)

•  ensure o-ring is in place, check for cuts or 

abrasions, clean o-ring, moisten with water/ 

lubricant and re-install, replace if necessary 

(410867)

Condensation on  

reactor chamber caused 

by excessive  humidity 

& cold water

•  check location of disinfection system and 

control humidity

Inadequate inlet/outlet  

port connections

•   check thread connections, reseal with Teflon

®

 

tape and re-tighten

System 
Shutting Down 
Intermittently

Interrupted power 

supply

•  ensure system has been installed on its own 

circuit, as other equipment may be drawing 

power away from UV (ie. pump or fridge)

•  UV system should not be installed on a circuit 

which is incorporated into a light switch

Lamp Failure 
Alarm on - 
New Lamp

Loose connection  

between lamp and  

connector

•  disconnect lamp from connector and 

reconnect, ensuring that a tight fit is 

accomplished

Moisture build up in    

connector may keep 

lamp and connector 

from making a solid 

connection

•  eliminate chance of any moisture getting to 

the connector and/or lamp pins

10

Summary of Contents for Aquasana SC200-A

Page 1: ...Owner s Manual Installation Operation and Maintenance 520192 R_RevA Aquasana Inc 6310 Midway Road Haltom City TX 76117 CUSTOMER SERVICE Mon Fri 8am 8pm CST 866 NO BOTTLE 866 662 6885 ...

Page 2: ...eved Aquasana Powered by Sterilight lamps are LongLife coated for stability longer life and increased efficiency Even lamps that look the same will not perform the same Get water confidence with genuine lamps proven to disinfect over their entire lifetime Environmentally friendly With less than 10mg of mercury 70 per cent less than most other commercially available lamps Toxicity Characteristic Le...

Page 3: ... have taken the first step in ensuring the safety of your water supply by using a totally non intrusive physical disinfection method Your Aquasana Powered by Sterilight system uses the most advanced UV technology on the market and is de signed to provide you with years of trouble free operation with minimal maintenance required ...

Page 4: ...tenance on UV Chamber unless UV chamber has been isolated and depressurized Never service UV Lamps Sleeves or associated hardware until depressurization of UV chamber has been confirmed Hot chamber Allow UV Lamps UV Chamber to cool for a minimum of 10 minutes before handling Cut or ingestion Ensure the quartz sleeve or lamp is not broken cracked or damaged in any way when handling equipment Scald ...

Page 5: ...gile Eye Protection WEEE waste electrical or electronic equipment This symbol indicates that you should not discard wasted electrical or elec tronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center ...

Page 6: ...TH AMERICAN NEMA 5 15P 3 PRONG GROUNDED 602637 CONTINENTAL EUROPEAN CEE 7 7 2 PIN WITH GROUND SCHUKO 260012 UK VERSION BS 1363 3 PRONG GROUNDED 5 AMP FUSE 260013 AUSTRALIAN VERSION AS 3112 3 PRONG GROUNDED 260019 NO CONNECTOR 3 WIRE BARE LEADS lamp connector 1 gland nut RN 001 o ring 410867 214 fused quartz sleeves with fire polished ends QS 001 FOR SC200 A QS0 410 FOR SC410 A Controller POWER 100...

Page 7: ...e condition 8 Intended for indoor use only Do not install this disinfection system where it will be exposed to the weather or to temperatures below freezing Do not store this disinfection system where it will be exposed to the weather Do not store this disinfection system where it will be exposed to temperatures below freezing unless all water has been drained from it and the water supply has been...

Page 8: ...ion system is designed to be mounted either horizontally or vertically at the point of use or point of entry depending on the specific flow rate of the unit Note The ideal installation is vertical with the lamp connector on top This is to prevent water damage from occurring on the lamp pins and lamp connector The ballast should be mounted either above or beside the reactor chamber Never mount vert...

Page 9: ...itable location for the disinfection system and its related components As it is recommended to install a ground fault protected circuit GFCI make sure that this is taken into consideration prior to any installation The system can either be installed vertically inlet port at the bottom Figure 1A or horizontally however the vertical installation is the most preferred method When selecting a mounting...

Page 10: ...ks The most likely cause for leaks is from the o ring seal In case of a leak shut water off drain cell remove the retaining nut wipe the o ring and threads clean and re install 7 Once it is determined that there are no leaks plug the system into the ground fault interrupter and check controller to ensure the system is operating properly The controller is designed to detect both power to the system...

Page 11: ...ations have passed the chlorine disinfection solution you will need to leave the solution sit for a period of 20 30 minutes Reinstall the pre filter cartridge into the filter and then flush the chlorine solution from the system until no chlorine smell is detectable Make sure that each fixture that was disinfected in step two is completely flushed of the chlorine solution as the consumption of this...

Page 12: ...ouching the lamp on the glass portion Handling the lamp at the ceramic ends is acceptable however if you must touch the lamp glass please use gloves or a soft cloth Fully remove the lamp from the reactor chamber being careful not to angle the lamp as it is removed from the chamber If the lamp is removed on an angle pressure will be applied on the inside of the quartz sleeve causing the sleeve to f...

Page 13: ...o the lamp connection do not allow quartz sleeve to fall d Carefully remove o rings from the quartz sleeve Figure 3A As the o ring may tend to adhere to the quartz sleeve it is recommended to replace the o rings annually Remove quartz sleeve carefully from chamber e Clean the outside of the quartz sleeve with a cloth soaked in CLR vinegar or some other mild acid and then rinse f Re assemble the qu...

Page 14: ...p from the reactor chamber refer to www lamprecycle org for lamp disposal 3 install new UV lamp and connect it to lamp connector refer to page 7 4 replace lamp connector 5 hold down the RESET switch while reapplying power to the controller until you see rSEt then release 6 5 second delay will occur until you hear an audible tone LED display will read once again Once you hear the tone let go of the...

Page 15: ...oblem caused by infrequent use of water run water until it return to ambient temperature install temperature management valve Water Appears Milky Caused by air in the water lines run water until air is purged Chamber Leaking Water Problem with o ring seal on gland nut and or UV sensor ensure o ring is in place check for cuts or abrasions clean o ring moisten with water lubricant and re install rep...

Page 16: ...to confirm that the controller is able to power lamp check to see if there is sufficient power to the UV system Dose Flow Chart 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 45 FLOW R ATE U S g pm UV DOSE FLUENCE mJ cm2 SC200 A SC410 A Note dosages based on 95 UVT at end of lamp life 0 80 EOLL 1966 US Public Health Manufacturers Standard NSF EPA Standard AquaSana Series Dose Chart E Coli eradi...

Page 17: ...PT 1 FNPT Combo 3 4 FNPT 1 MNPT Shipping Weight 5 1kg 11 3lbs 6 8kg 15 0lbs Electrical Voltage 100 240V 50 60Hz 100 240V 50 60Hz Power Consumption 35 W 60 W Lamp Watts 27 W 46 W Maximum Operating Pressure 8 62bar 125psi 8 62bar 125psi Ambient Water Temperature 2 40 C 36 104 F 2 40 C 36 104 F LampType Sterilume HO high output Sterilume HO high output Visual Power On Yes Yes Audible Lamp Failure Yes...

Page 18: ...ch mounting brackets to the wall Mount UV filter Direction of flow To House Attach the male end of the flex hose to the UV inlet Use Teflon tape Attach the female end of the flex hose to 4 threaded nipple Use Teflon tape Position control module to allow for a drip loop on the cord 1 2 3 4 5 Rhino Whole House Water Filter ...

Reviews: