9.2.1 System image
;1.1: System image active: 1, inactive: 0
system_active = 1
System_active is preset in the factory to 1, so the system image can be selected and displayed in the
digital picture frame.
If system_active is set to 0, the system image cannot be selected in the digital picture frame.
9.2.2 Time diagram
;1.2: Time diagram active: 1, inactive: 0
diagram_active = 1
Diagram_active is preset in the factory to 1, so the daily diagram can be selected and displayed in the
digital picture frame.
If diagram_active is set to 0, the daily diagram cannot be selected in the digital picture frame.
9.2.3 Sensor selection for temperature diagram
;1.3 Override bitmask for inputs (T6|T5|T4|T3|T2|T1) e.g. "0|0|1|1|1|1"
;diagram_bitmask_override = "0|0|1|1|1|1"
The selection of the temperature sensors which are shown in the temperature diagram can be changed.
To do so, the semicolon before the phrase "diagram_bitmask_override" must be deleted and a sensor
selection must be defined as shown in the example. The selection is defined using six characters, each
separated by a "|". The characters may only have the value "0" or "1"; "0" means sensor "not selected",
and 1 means sensor "selected".
In the example "0|0|1|1|1|1", the sensors T1 to T4 would be selected, while T5 and T6 would be
deactivated.
If you wish to return to the standard settings, you must re-write a semicolon in front of the phrase
"diagram_bitmask_override".
9.2.4 CO
2
factor
;1.4 Override CO2 factor
;factor_CO2 = 0.232
If you wish to use another factor than 0.232 Kg/kWh to calculate the CO2 value, this factor can be
defined.
To do so, the semicolon in front of the phrase "factor_CO2" must be deleted and a factor defined as
shown in the example. The physical unit of the factor is kg/kWh.
If you wish to return to the standard settings, you must re-write a semicolon in front of the phrase
"factor_CO2".
9.2.5 Diagram title
;1.5: Diagram title (50 characters)
diagram_title = ""
You can specify a title for the temperature diagram which is shown above the temperature curves. The
diagram title is limited to a maximum of 50 characters.
diagram_title is set to "" at the factory, i.e. a title is not defined.
The title is defined by entering characters within the quotations marks, e.g. diagram_title = "My solar
energy system"
9.2.6 Diagram legend
;1.6: Texts for diagram legend (12 characters)
diagram_t1_text ="T1"
diagram_t2_text = "T2"
diagram_t3_text = "T3"
diagram_t4_text = "T4"