background image

18

SELF DIAGNOSTIC CONTROLLER

This controller is designed for ignition lockout after three consecutive
failed attempts to light. If lockout occurs, the display lights will match
Figure 17. Along with this, a numeric message will appear in the
display. The following list of ERROR CODES illustrates possible
numeric failures.

FIGURE 17.

GAS VALVE LED FLASHING

This condition results from a failure to establish burner ignition after
three successive trials. In such cases:

1. Investigate the possible cause and remedy any observations.

2. Momentarily depress the button on the display panel to reset the

lockout condition.

3. Confirm proper appliance operation.

Possible Cause

Remedy

1. Burner ground wire broken

1. Check wire and connection

or corroded

at burner

2. Connectors unplugged

2. Check connections

3. Igniter broken

3. Replace igniter

4. Flame probe faulty

4. Replace flame probe

5. Gas shut off

5. Turn on gas supply

6. Clogged gas valve

6. Replace gas valve

7. Faulty gas valve

7. Replace gas valve

8. Defective control

8. Replace control

9. Burner improperly adjusted

9. Adjust burner

10. Dirty burner

10. Clean burner

OPERATION

SEQUENCE OF OPERATION

Typical Control/Appliance Operating Sequence

1.

When the control is powered, it should first display “0”, then
the input line voltage (“120”), the calibration setting (12), then
the actual water temperature in the tank.

2.

If the control determines that the actual water temperature inside
the tank is below the programmed temperature setpoint less
the differential, a call for heat is activated.

3.

The control then performs selected system diagnostic checks.
This includes confirming the proper state of the air switches
and ECO limit device.

4.

If all checks are successfully passed, the combustion blower is
energized for the pre-purge cycle.

5.

When the pre-purge cycle is complete, power is applied to the
ignitor element for the ignitor warm-up period.

6.

At the conclusion of the igniter warm-up period, the gas valve
will open, allowing gas to enter the burner chamber.

7.

The igniter will remain on for a short predetermined time period,
then will be turned off.

8.

After an additional 2 seconds, the control will monitor the flame
sense probe to confirm a flame is present. If a flame is not
verified within this time period, the gas valve will immediately
be closed, and the blower will continue to run for approximately
10 seconds. The control will then return to step 2.

9.

If a flame is confirmed, the control will enter the heating mode
where it will continue heating the tank water until the setpoint
temperature plus differential is reached. At this point, the gas
valve is closed and the control enters the post-purge cycle.

10. The combustion blower will run for the duration of the post purge

cycle to purge the system of all combustion  gases. When the
post purge cycle is complete, the blower is
de-energized and will coast to a stop.

11. The control will now enter the idle state while continuing to

monitor the internal tank water temperature and the state of
other system devices. If the temperature drops below the
setpoint value less differential, the control will automatically
return to step 2 and repeat the entire operating cycle. During
this idle state, if the control detects an improper operating state
for external devices such as the ECO switch, vent switch,
pressure switch, etc., the appropriate LED(s) on the Display
Board will be illuminated indicating the nature of the fault.

Summary of Contents for ULTRA FORCE SUF-130-300

Page 1: ...D USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing prope...

Page 2: ...n Code and CSA C22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 NFPA documents are also availabl...

Page 3: ...18 Gas Value LEDs Flashing 18 Error Codes 19 Fault Conditions 19 No Incoming Line Voltage 19 No Low Voltage 19 Temperature Probe Fault 19 20 E C O Switch Open 20 Control Bad 20 Combustion Air Blockag...

Page 4: ...4 AT A GLANCE QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Page 5: ...ider using lower temperature settings to reduce scald hazards Temperature Time to Produce 2nd 3rd Setting Degree Burns on Adult Skin 180 F 82 C Nearly instantaneous 170 F 77 C Nearly instantaneous 160...

Page 6: ...a storage tank used in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National E...

Page 7: ...If the unconfined space is within a building of tight construction buildings using the following construction weather stripping heavy insulation caulking vapor barrier etc air for combustion and vent...

Page 8: ...RECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECO...

Page 9: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Page 10: ...tional Fuel Gas Code and local Codes IMPORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMI...

Page 11: ...e about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent terminal 7...

Page 12: ...the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to use a minimum of 0 equivalent feet of 4 inch PVC pipe IMPORTANT When multiple uni...

Page 13: ...a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner the pressure switch will allow the electrical contacts to close The pressure sw...

Page 14: ...PPLIERS REFER TO THE NATIONAL FUEL GAS CODE OR THE NATURALGAS AND PROPANE INSTALLATION CODE CSA B149 1 FIGURE 14 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only N...

Page 15: ...ystems ANSI Z21 22 CSA 4 4 Your local code authority may have other specific relief valve requirements WARNING THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEA...

Page 16: ...GH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY The controller is wired to the heater a...

Page 17: ...17 FIGURE 16...

Page 18: ...ng the proper state of the air switches and ECO limit device 4 If all checks are successfully passed the combustion blower is energized for the pre purge cycle 5 When the pre purge cycle is complete p...

Page 19: ...mplemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed State...

Page 20: ...t a control problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiri...

Page 21: ...ON OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYAND ELECTRICAL WORKARE REQUIRED Before attemp...

Page 22: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Page 23: ...CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 F...

Page 24: ...the hardness lime For this reason it is recommended that a regular schedule for deliming be maintained The depth of lime buildup should be measured periodically Heaters will have about 3 7 6cm of lim...

Page 25: ...e freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended size as necessary Inspection of the valve should be performed at least ever...

Page 26: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Page 28: ...CIFICATIONS PAGE 30 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Page 29: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Page 30: ...E 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE...

Page 31: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Page 32: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WATE...

Page 33: ...nate the problem replace the pressure switches 5 Check to see if there is resistance across the igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replace...

Page 34: ...ed immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 r...

Page 35: ...method d This warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by att...

Page 36: ...36 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: