State Water Heaters ULTRA FORCE SUF-130-300 Installation, Operation & Service Manual Download Page 33

33

Checking these four (4) items first will often result in a timely solution
to the service call.

  

WARNING

JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH
THE UNIT’S OPERATING SEQUENCE AND IGNITION SAFETY.
IF YOU DO NOT HAVE THE PROPER TEST EQUIPMENT, I.E. A
VOLT-OHM METER AND A MICROMETER, DO NOT ATTEMPT TO
TROUBLESHOOT OR REPAIR A.O. SMITH EQUIPMENT.

ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING
IN ANY WAY COULD RESULT IN INTERNAL DAMAGE TO THE
MODULE CIRCUITS, POSSIBLY ALTERING THE IGNITION
SEQUENCE ALLOWING GAS VALVES TO OPEN BEFORE THE
HOT SURFACE IGNITER IS UP TO IGNITION TEMPERATURE.

NOTE: ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES
WILL RESULT IN VOIDING THE APPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the
particular appliance.

Refer to the SEQUENCE OF OPERATION and the connection
diagram located on page 16 before continuing.

Make sure the appliance is connected to a 120V AC power supply,
manual gas valve is in the ON position, and all electrical connections
are secure before continuing to troubleshoot this appliance.

  

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT
SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES ZERO
VOLTAGE.

MOTOR WILL NOT RUN

1. Confirm 120V AC. Also, to verify correct polarity, check for 120 V

AC between hot supply and ground. If there is no voltage, check
for a loose connection.

2. For SUF 130 400, a VFD (Variable Frequency Drive) is used.

"rdy" (stands for ready) will be shown on display in standby
heating mode. "152" (152 output Hz) shall be shown on VFD
display during heater running. Any other display (other than "rdy"
or "152") indicates the VFD fault. Check 120V AC to the VFD
power input L1 and N terminals. Check the open contact of the
relay (mounted on VFD) wired to VFD te15V and LI1.
When calling for heat, the relay should be energized, the relay
contact will change from "open" to "close", and VFD display will
change from "rdy" to "152", and blower starts to run. If there's no
display change (from "rdy" to "152") on VFD during the call for
heat, check the wire from the controller blower connector to the
relay A1 and A2 terminal or replace the relay coil.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT

MAIN FLAME NOT ESTABLISHED

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check

for blockage in the intake and exhaust venting or at the vent
hoods. If no blockage is found, check vinyl tubing for cuts or
crimps. If this tubing is damaged it must be replaced. If these
steps do not eliminate the problem, replace the pressure switches.

5. Check to see if there is resistance across the igniter terminal

with an OHM meter. If there is no continuity, the igniter is broken
and should be replaced.

If the igniter appears to function properly, then verify that the inlet
pressure is 11.0" Natural Gas (2.74 kPa).  The gas valve supplied
on this appliance is not designed to open against a higher pressure.
At this time also check that the inlet pressure is not lower than the
minimal gas supply pressure, as shown in Table 4: that is, for
Natural Gas, 5.2" (1.29 kPa) W.C. If the inlet pressure is not within
these limits then adjust the supply pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify
that the manifold pressure, when the gas is fully open, with the
heater running, is as called out in Table 4:  that is, for Natural
Gas, 4.0" (0.996 kPa)  W.C.  If the manifold pressure is not correct
then adjust accordingly.  See ADJUSTMENT PROCEDURE in
OPERATING INSTRUCTIONS selection, page 19, for the
manifold pressure adjustment procedure.

6. If the inlet and manifold pressures are within the limits specified

in step 5, then reset the appliance. Verify 24V AC at the gas
valve during the three (3) second ignition trial, after the igniter
reaches operating temperature. If 24V AC at the gas valve is not
seen during this period, the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition
trial and the manifold pressure does not increase above 0" W.C.
then verify that the manual gas control valve is in the “ON” position
(see page 20). If the valve is in the “ON” position and the previous
voltage and gas pressure conditions are met, then the gas valve
is defective and must be replaced.

Note that a positive manifold pressure reading of approximately
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the
ignition cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air

has been purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition,

verify that the inlet pressure is not greater than 11.0" (2.74 kPa)
W.C. or lower than the minimal gas supply pressure, as shown
in Table 4: that is, for Natural Gas, 5.2" (1.29 kPa) W.C.  pressure.
Also, the manifold pressure should rise during the three (3)
second trial for ignition to the manifold pressure value for the
individual unit listed in Table 4: that is, for Natural Gas,
4.0" (0.996 kPa) W.C. If the manifold pressure is not correct then
adjust accordingly. See ADJUSTMENT PROCEDURE in
OPERATING INSTRUCTIONS section, page 19, for the manifold
pressure adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller

is polarity sensitive. If the hot and neutral supply wires are
reversed, the controller will not sense flame. Reverse the supply
wires and try to fire the unit.

Summary of Contents for ULTRA FORCE SUF-130-300

Page 1: ...D USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing prope...

Page 2: ...n Code and CSA C22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 NFPA documents are also availabl...

Page 3: ...18 Gas Value LEDs Flashing 18 Error Codes 19 Fault Conditions 19 No Incoming Line Voltage 19 No Low Voltage 19 Temperature Probe Fault 19 20 E C O Switch Open 20 Control Bad 20 Combustion Air Blockag...

Page 4: ...4 AT A GLANCE QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Page 5: ...ider using lower temperature settings to reduce scald hazards Temperature Time to Produce 2nd 3rd Setting Degree Burns on Adult Skin 180 F 82 C Nearly instantaneous 170 F 77 C Nearly instantaneous 160...

Page 6: ...a storage tank used in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National E...

Page 7: ...If the unconfined space is within a building of tight construction buildings using the following construction weather stripping heavy insulation caulking vapor barrier etc air for combustion and vent...

Page 8: ...RECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECO...

Page 9: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Page 10: ...tional Fuel Gas Code and local Codes IMPORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMI...

Page 11: ...e about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent terminal 7...

Page 12: ...the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to use a minimum of 0 equivalent feet of 4 inch PVC pipe IMPORTANT When multiple uni...

Page 13: ...a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner the pressure switch will allow the electrical contacts to close The pressure sw...

Page 14: ...PPLIERS REFER TO THE NATIONAL FUEL GAS CODE OR THE NATURALGAS AND PROPANE INSTALLATION CODE CSA B149 1 FIGURE 14 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only N...

Page 15: ...ystems ANSI Z21 22 CSA 4 4 Your local code authority may have other specific relief valve requirements WARNING THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEA...

Page 16: ...GH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY The controller is wired to the heater a...

Page 17: ...17 FIGURE 16...

Page 18: ...ng the proper state of the air switches and ECO limit device 4 If all checks are successfully passed the combustion blower is energized for the pre purge cycle 5 When the pre purge cycle is complete p...

Page 19: ...mplemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed State...

Page 20: ...t a control problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiri...

Page 21: ...ON OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYAND ELECTRICAL WORKARE REQUIRED Before attemp...

Page 22: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Page 23: ...CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 F...

Page 24: ...the hardness lime For this reason it is recommended that a regular schedule for deliming be maintained The depth of lime buildup should be measured periodically Heaters will have about 3 7 6cm of lim...

Page 25: ...e freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended size as necessary Inspection of the valve should be performed at least ever...

Page 26: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Page 28: ...CIFICATIONS PAGE 30 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Page 29: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Page 30: ...E 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE...

Page 31: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Page 32: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WATE...

Page 33: ...nate the problem replace the pressure switches 5 Check to see if there is resistance across the igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replace...

Page 34: ...ed immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 r...

Page 35: ...method d This warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by att...

Page 36: ...36 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: