State Water Heaters ULTRA FORCE SUF-130-300 Installation, Operation & Service Manual Download Page 32

32

CHECKLIST AND SERVICE INFORMATION

IMPORTANT

The installer may be able to observe and correct certain problems
which might arise when the unit is put into operation or when it is re-
fired after a prolonged shutdown. HOWEVER, it is recommended
that only qualified servicemen, using appropriate test equipment,
be allowed to service the heater.

BE SURE TO TURN OFF THE ELECTRICITY WHENEVER
POSSIBLE OR APPROPRIATE WHILE CHECKING EQUIPMENT.

  

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.

  

CAUTION

:

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

BURNER OPERATIONAL PROBLEMS

 1. Refer to TROUBLESHOOTING.

NOT ENOUGH OR NO HOT WATER

1. Be certain the electrical disconnect switch serving the water

heater is in the ON position.

2. Check the fuses.

• The electrical  disconnect switch usually contains fuses.

3. The capacity of the heater may have been exceeded by a large

demand for hot water.

• Large demands require a recovery period to restore water

temperature.

4. Colder incoming water temperature will lengthen the time

required to heat water to the desired temperature.

• If the heater was installed when incoming water

temperature was warm, colder water creates the effect of
less hot water.

5. Look for hot water wastage and leaking or open hot water

faucets.

6. Sediment or lime scale may be affecting water heater operation.

Refer to MAINTENANCE for details.

7. The heater’s temperature high limit sensor has activated. Press

the reset button on the thermostat.

8. Burner may not be firing at proper rate.

• Check gas pressure. Adjust to obtain required manifold

pressure.

9. Burner fan wheel may be dirty.

• Clean fan wheel with a stiff brush.

10. Condensate hose may be blocked where it connects to the

exhaust elbow.

• Verify the condensate drains from the unit without restriction.

WATER IS TOO HOT

1.

Refer to WATER TEMPERATURE CONTROL.

WATER HEATER MAKES SOUNDS

1.

Sediment or lime scale accumulations cause rumbling and
pounding noises when the heater is operating.

• The sounds are normal, however, the tank bottom should be

cleaned.  Refer to MAINTENANCE for details.

2.

Some of the electrical components of the water heater make
sounds which are normal.

• Contacts click or snap as the heater starts and stops.

• Transformers often hum.

WATER LEAKAGE IS SUSPECTED

1.

Check to see if the water heater drain valve is tightly closed.
Also check the cleanout opening for leakage.

2.

The apparent leakage may be condensation which forms on
cool surfaces of the heater and piping.

3.

If the outlet of the relief valve is leaking it may represent:

• Excessive water pressure.

• Excessive water temperature.

• Faulty relief valve.

Excessive water pressure is the most common cause of relief valve
leakage. It is often caused by a “closed system”. If a check valve is
in the inlet system it will not permit the expanded hot water volume
to equalize pressure with the main. The relief valve must release
this water or the water heater or plumbing system will be damaged.
Refer to MAINTENANCE-RELIEF VALVE section in this manual.

When such a condition is encountered, local codes or inspection
agency should be consulted to determine which system is acceptable
in your area.  See CLOSED SYSTEM section in this manual.

TROUBLESHOOTING

1.

Verify that the allowable vent length has not been exceeded and

that the blower inlet screen has been removed if direct venting.

2.

Verify the gas supply volume and pressure per table 3 and 4.

3.

Verify that the condensation, which WILL be present in the

heater and exhaust vent, will drain.

4.

Check supply wire polarity - hot to hot and neutral to neutral

and no "stray" current in neutral.

5.

Heater is properly grounded.

Summary of Contents for ULTRA FORCE SUF-130-300

Page 1: ...D USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing prope...

Page 2: ...n Code and CSA C22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 NFPA documents are also availabl...

Page 3: ...18 Gas Value LEDs Flashing 18 Error Codes 19 Fault Conditions 19 No Incoming Line Voltage 19 No Low Voltage 19 Temperature Probe Fault 19 20 E C O Switch Open 20 Control Bad 20 Combustion Air Blockag...

Page 4: ...4 AT A GLANCE QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Page 5: ...ider using lower temperature settings to reduce scald hazards Temperature Time to Produce 2nd 3rd Setting Degree Burns on Adult Skin 180 F 82 C Nearly instantaneous 170 F 77 C Nearly instantaneous 160...

Page 6: ...a storage tank used in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National E...

Page 7: ...If the unconfined space is within a building of tight construction buildings using the following construction weather stripping heavy insulation caulking vapor barrier etc air for combustion and vent...

Page 8: ...RECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECO...

Page 9: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Page 10: ...tional Fuel Gas Code and local Codes IMPORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMI...

Page 11: ...e about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent terminal 7...

Page 12: ...the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to use a minimum of 0 equivalent feet of 4 inch PVC pipe IMPORTANT When multiple uni...

Page 13: ...a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner the pressure switch will allow the electrical contacts to close The pressure sw...

Page 14: ...PPLIERS REFER TO THE NATIONAL FUEL GAS CODE OR THE NATURALGAS AND PROPANE INSTALLATION CODE CSA B149 1 FIGURE 14 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to flange only N...

Page 15: ...ystems ANSI Z21 22 CSA 4 4 Your local code authority may have other specific relief valve requirements WARNING THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEA...

Page 16: ...GH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY The controller is wired to the heater a...

Page 17: ...17 FIGURE 16...

Page 18: ...ng the proper state of the air switches and ECO limit device 4 If all checks are successfully passed the combustion blower is energized for the pre purge cycle 5 When the pre purge cycle is complete p...

Page 19: ...mplemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed State...

Page 20: ...t a control problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiri...

Page 21: ...ON OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYAND ELECTRICAL WORKARE REQUIRED Before attemp...

Page 22: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Page 23: ...CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 F...

Page 24: ...the hardness lime For this reason it is recommended that a regular schedule for deliming be maintained The depth of lime buildup should be measured periodically Heaters will have about 3 7 6cm of lim...

Page 25: ...e freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended size as necessary Inspection of the valve should be performed at least ever...

Page 26: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Page 28: ...CIFICATIONS PAGE 30 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Page 29: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Page 30: ...E 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE...

Page 31: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Page 32: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WATE...

Page 33: ...nate the problem replace the pressure switches 5 Check to see if there is resistance across the igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replace...

Page 34: ...ed immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 r...

Page 35: ...method d This warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by att...

Page 36: ...36 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Reviews: