Flue gas outlet
Release R.1.0 Uk
29
is
3.9.1
Introduction
When connecting the appliance to the flue gas outlet duct one must use the
draught diverter
that is supplied. The standard flue gas thermostat and
sensor that are supplied should be fitted in the
3.9.2
Fitting the draught diverter
The draught diverter
is fastened using two fastening screws
procedure is as follows:
1. Place the draught diverter on the appliance and mark the drill holes.
Remove the draught diverter from the appliance.
n
Remark
The position of the holes already made for the flue gas cut-out sensor must
be taken into account. The holes must be roughly in line with the flue gas
thermostat bracket.
2. Now drill two holes into the top of the appliance (3.2 mm drill bit).
3. Using the fastening screws, fix the draft limiting device to the appliance.
4. Fit to the opening of the draft limiting device a vertical flue gas outlet
pipe flue gas outlet pipe
measuring at least 0.5 metres and then fit the rest
of the flue gas outlet materials in accordance with the current regulations.
See paragraph
n
Remark
Use flue gas outlet parts that comply with the regulations. See paragraph
n
Remark
Make sure that the flue gas outlet is fitted in a discharge area in which it is
is permitted for the relevant category of appliance.
Legend
a
draught diverter
b
fastening screws
c
flue gas outlet pipe
Figure 3.4
Fitting the draught diverter
IMD-0148
> 0,5 m
Summary of Contents for SCE 65-400
Page 2: ...your installer ...
Page 4: ...4 SCE Instruction Manual ...
Page 8: ...8 Instruction Manual SCE gis ...
Page 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Page 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Page 42: ...Installation 42 Instruction Manual SCE 3 is ...
Page 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Page 64: ...Maintenance 64 Instruction Manual SCE 9 s ...