Installation
26
Instruction Manual SCE
3
is
3.6
Water connections
Unvented
3.6.1
Cold water side
See
1. On the cold water side fi
t
an approved stop valve
regulations in force.
See also paragraph
2. The maximum working pressure of the appliance is 8 bar. Because the
pressure in the water pipe might sometimes be higher than 8 bar, you will
have to fit an approved pressure pressure reduction valve
3. Fit a non-return valve
and an expension vessel
4. Fit a pressure pressure overflow valve
and connect the overflow side to
an open water drain pipe.
3.6.2
Shunt pipe
You can connect a shunt pump to prevent stacking of the water in the
waterheater.
1. Optional: fit a shunt pipe depending on the tap design (Ø 22 mm), a stop
and a shunt pump shunt pump
.
2. Fit a non-return valve
.
3. Fit a stop valve
3.6.3
Hot water side
See
n
Remark
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve
1. Optional: fit a temperature gauge
to check the temperature of the tap
water.
2. Fit a stop valve
in the hot water outlet pipe for servicing.
3.6.4
Drain valve
1. Fit the standard drain valve
supplied.
2. Refer to paragraph
if a circulation pipe is to be fitted. Otherwise, fit the
sealing nut supplied with the drain valve complete with packing. See
Summary of Contents for SCE 65-400
Page 2: ...your installer ...
Page 4: ...4 SCE Instruction Manual ...
Page 8: ...8 Instruction Manual SCE gis ...
Page 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Page 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Page 42: ...Installation 42 Instruction Manual SCE 3 is ...
Page 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Page 64: ...Maintenance 64 Instruction Manual SCE 9 s ...