Installation
53796
3-27
3.9.2
Mounting the VIP-125
The VIP-125 is equipped with a separate enclosure. Refer to Section 3.1 when selecting a
mounting location for the VIP-125.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the
center of the building as possible and located within a secured area, but should be accessible
for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on
concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the
concrete surface and then attach the cabinet to the plywood. Also mount any other modules to
the plywood.
The cabinet can be surface or flush-mounted. If you will be flush-mounting the cabinet, the
hole for the enclosure should be 14.5" W x 24.75" H x 3-7/16” D (36.8cm W x 62.9cm H x
8.73cm D). Do not flush-mount in a wall designated as a fire break. The Outside dimensions
of the cabinet are 16" W x 26-1/4” H x 4-1/8” D (40.64cm W x 66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. On the mounting surface install two screws level with each other 11" apart
Figure 3-27 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2. Install the cabinet onto the two mounting screws and tighten the screws.
3. Insert two screws into the two bottom mounting holes.
Bottom Mounting Holes
Key Holes
Board mounting
bracket
Summary of Contents for SCSS-700VS
Page 2: ......
Page 14: ...VIP Series Voice Integration Package Installation Operation Manual 1 8 53796...
Page 72: ......
Page 73: ......
Page 74: ......