Installation
53796
3-25
3.8.9
Calculating Current Draw and Standby Battery
This section helps you determine the current draw and standby battery needs for your
installation (18 Ampere Hours max. will fit in cabinet). Complete the remaining instructions
in Table 3-2.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be housed in the
RBB Accessory Battery Cabinet. Maximum of 33 Ampere Hours per system.
Table 3-2. Current Draw Calculations
Device
No. of
Devices
Current Per Device
Standby
Current
Alarm
Current
VIP-50
1
Standby:
75 mA
75 mA
Alarm:
700 mA
700 mA
VIP-CE4
0 or 1
Standby:
20 mA
Alarm (All Channels):
180 mA
mA
A
Current Subtotals:
mA
mA
Notification Devices
Refer to device manual for number of devices and current ratings.
B
Current Subtotals:
mA
mA
C Total current rating of all devices in system (Line B) X .001
A
A
D Number of standby hours (24 or 60 for NFPA 72)
H
E Multiply line C (standby current) and D:
Total standby AH
AH
F Alarm sounding period in hours (For example, 5 minutes = .0833 hours):
H
G Multiply line C (alarm current) and F:
Total alarm AH
AH
H Add lines E and G (AH = Ampere Hours):
Total AH required
AH
Summary of Contents for SCSS-700VS
Page 2: ......
Page 14: ...VIP Series Voice Integration Package Installation Operation Manual 1 8 53796...
Page 72: ......
Page 73: ......
Page 74: ......