VIP-Series Voice Integration Package Installation/Operation Manual
2-2
53796
2.2
Underwriters Laboratories (UL)
2.2.1
Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on).
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in FACP installation manual.
3. Use UL listed notification appliances compatible with the FACP from those specified in
the
Appendix
at the back of this manual.
4. UL installations using Class B wiring for the speaker circuit require the use of a Model
7630 EOL resistor assembly.
5. A full system checkout must be performed any time the panel is programmed.
2.2.2
Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FACP sends an automatic
daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3
Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
1. Do not exceed the current load restrictions shown in FACP installation manual.
2. The AC Loss Hours option must be set from 1-3 hours.
The VIP-Series Control is UL listed as a voice evacuation unit for use in NFPA 72 systems. If
the VIP-Series Control and its accessories are to be used as part of a UL installation, carefully
read the UL requirements in this section. For more information on NFPA 72 standards, refer to
the
NFPA National Fire Alarm Code
.