background image

TDM

Universal Time Delay Module 

INSTALLATION INSTRUCTIONS

8701 Castle Park Drive 

„

 Indianapolis, Indiana 46256

Telephone: (800) 842-2545/(317) 842-2545 

„

 www.mssedco.com 

„

 [email protected]

Page 1

(82A044)  TDMv0605

Section 1

General Description

The TDM is a multipurpose timing module that can be 
used for a variety of applications.  Its unique design and 
open architecture allows the TDM to be used in any 
application that requires timing control of up to two 
outputs with up to four inputs.  Common applications 
include: simple time delay, vestibule door sequencing 
(only one device required) and electric lock/automatic 
door operator sequencing.

The four inputs on the TDM allow sequencing or 
independent operation of the two outputs.  Input 1 will 
sequence Outputs 1 then 2.  Input 2 will sequence 
Outputs 2 then 1.  Input 3 will operate Output 1 
independently.  Input 4 will operate Output 2 
independently. 

Both outputs on the TDM are fully programmable for "on 
time" duration as well as the delay time between the two 
outputs from 0 to 99 seconds.  

 

 

CAUTION: 

 Devices to be controlled by the TDM

 

must be low voltage (12-24V) but can be 

 

inductive loads.  Surge suppressors are standard 

 

on the TDM. 

WET/DRY CONTACT OPTION:

The TDM has the option to supply power to Relay Output 
1 contacts.  This is known as having a "Wet" contact 
instead of the conventional "Dry" contact closure.  To use 
output 1 as a "Wet" contact, change the jumper setting 
(see Figure 1).  The voltage supplied to Output 1 will be 
the same as the voltage supplied to the input power wires 
of the TDM.

 

WARNING: 

 Changing jumper settings to enable 

 

the “Wet” Contact option will apply a voltage to 

 

the Output 1 relay contact. Please ensure that 

 

any device connected to this output is capable of 

 

accepting voltage. Failure to do so may result in 

 

damage to the device.

Section 2

Basic Installation

The physical placement of the TDM is typically in the door 
operator housing area since the power supply and 
operator control are already in this location.  The TDM 
layout and wiring connections are shown in Figure 1.

Included on the following pages are detailed wiring and 
programming instructions for three common applications.

  Figure 2:  Simple Time Delayed Output
  Figure 3:  Electric Lock & Door Operator Sequencing
  Figure 4:  Vestibule Door Sequencing

After successfully wiring the TDM for your application, 
refer to Figure 5 for the operating display explanations 
and additional programming options.  For additional 
technical assistance, please contact us toll-free at 1-800-
842-2545.

 

NOTICE:

  These instructions are provided for your 

 

convenience.  Please verify your installation is in 

 

compliance with all local electrical codes.

Section 3

Technical Data

Model....................................... TDM
Input Power.............................. 12-24V AC or DC 
Power Consumption................ 2W Maximum
Output Contacts....................... Form C, Rated at 3 Amps
Relay Contact Rating............... 3A:120V AC; 3A:60V DC
Temperature Rating................ -22°F to 158°F 
 

(-30°C to 70°C)

Weight...................................... <0.25 lbs.
Physical Size............................ 4.75"L x 2.125"W x 0.75"H

Section 4

Warranty

MS SEDCO guarantees this product to be free from manufacturing 
defects for 1 year from date of installation.  Unless MS SEDCO is 
notified of the date of installation, the warranty will be in effect for 
1 year from the date of shipment from our factory.  If, during the 
first year, our motion detector or support device fails to operate 
and has not been tampered with or abused, the unit can be 
returned prepaid to factory and it will be repaired free of charge.  
After 1 year, the unit will be repaired for a nominal service charge.  

This limited warranty is in lieu of all other warranties expressed 
or implied, including any implied warranty of merchantability, 
and no representative or person is authorized to assume for MS 
SEDCO any other liability in connection with the sale of our 
products.  All warranties are limited to the duration of this 
written warranty.  In no event shall MS SEDCO be liable for any 
special, incidental, consequential or other damages arising 
from any claimed breach of warranty as to its products or 
services.

Questions?  Call us toll-free at 1-800-842-2545 or

visit us online at www.mssedco.com.

!

!

!

Summary of Contents for MA900n

Page 1: ...Bifold Swing Accessories Operators Drives Sensors Slide Class 2 Controls Panels Hardware Tech Tip Classification Adjustment Customer Complaints FAQs Retrofit Upgrade Instructions Installation Clarifications Service Design Change Description Release Action Level 1 Does not impact maintenance or operation of door Only Safety Liability and Engineering need to sign Level 2 Full sign off required Relea...

Page 2: ...None Information Only Inspection Required Where Symptom Exists New Installation Only Inspect During Maintenance Attached is the latest version of the MA900 Installation and Owner s Manual 203936 Rev C This manual has been revised to include the MS Sedco TDM Time Delay Module The changes can be found at the following places Page 16 Figures 21 and 22 Page 17 Figure 23 and Notes Page 22 Optional Sequ...

Page 3: ...MA900 Installation and Owner s Manual 203936 Rev C ...

Page 4: ... 2005 The STANLEY WORKS ALL RIGHTS RESERVED 203936 Rev C MA900 Installation Manual 2 ...

Page 5: ...ion Requirements 7 Items Supplied 8 Tools Required 9 Installation Procedures 10 Header Assembly Installation 10 Connect Actuation Devices 15 Power Requirements 15 Wiring Diagrams 16 Tune In Procedures 18 Optional Sequencing Timers 22 Safety Checks 23 Safety Decals 23 Troubleshooting 25 Warranty The MA900 Series is warranted against defects in material and workmanship for a period of one year from ...

Page 6: ...e applied to the door See Safety Decals section of this manual for information on applying these labels To reduce the risk of electrical shock connect the power wire to only a properly grounded outlet Never let children operate or play near the door Keep RF transmitters in a location inaccessible to children Misuse of a door actuation device may result in serious injury Operate the door only when ...

Page 7: ... manual provides you with the information you need to install the Stanley MA900 Door Operator The Stanley MA900 Installation Kit contains hardware components and materials required for a typical installation Make sure the operator you have select ed meets your application requirements The Stanley MA900 is available in four configurations see Figs 1 4 The electrical connection of the Stanley MA900 ...

Page 8: ... Swing Safe Technology The electronic safety control senses an obstruction during the opening cycle of the door The operator immediately reverses the door direction allowing time for the obstruction or person to clear the swing path area of the door Adjustable Time Delay When it reaches the fully open position the door pauses for a specified time before closing The time delay is adjustable and mus...

Page 9: ...4 If there is a manual closer it must be removed or made inoperable 5 The door must be in good working order The hinges must work properly the door must swing freely through its entire range 6 The frame must be made of 16 gauge welded steel or better or the mounting surface must be masonry or additional support must be provided behind the operator see Figs 5 and 6 7 For an outswing door the reveal...

Page 10: ...TANLEY WORKS ALL RIGHTS RESERVED 203936 Rev C MA900 Installation Manual 8 Items Supplied Operator Components The Stanley MA900 operator kit contains the following items see Fig 7 Fig 7 MA900 Operator Kit Contents ...

Page 11: ...ions Digital stopwatch Force gauge Number 2 Phillips screwdriver Small flat blade screwdriver 3 32 and 3 8 Allen wrenches Center punch Hammer Tape measure Diagonal cutters wire strippers Step ladder Electric drill 1 8 drill bit 25 64 drill bit 3 8 drill bit Tape for example electrical tape to hold template on door frame 1 2 box end wrench 5 8 box end wrench or adjustable wrench Carbide drill bits ...

Page 12: ...center punch to make a small depression on the frame at the center of the hole location marked C on the template 7 Remove the template 8 Use a 1 8 bit to drill a pilot hole at each hole location then use a 25 64 bit to drill each hole marked A out to the size of the Riv nut 9 Thread a Riv nut fully onto the Riv nut tool see Fig 9 The Riv nut tool is not supplied 10 Insert the Riv nut into a mounti...

Page 13: ...ter punch to make a small depression at the center of the hole location marked C on the template 7 Remove the template 8 Use a 1 8 bit to drill a pilot hole at each of the two hole locations marked D on the template 9 Drill the header mounting holes marked A and B to the desired size for mounting hardware not supplied 10 Install two mounting screws into lower left and lower right hand mounting hol...

Page 14: ...wer up 2 Set the mode switch to Hold Open The operator shaft rotates to its mechanical stop fully open and stays there Verify that the dowel pin on the operator shaft is against the stop see Fig 14 Fig 14 Full stop position If the operator shaft does not come to a full stop with the dowel pin against the stop decrease the back check time as described in step 2 of Door Opening Adjustments section o...

Page 15: ...manually pushing the door to its fully open position If the door opens to the desired angle go to Tune In Procedures section of this manual If the door does not open to the desired angle loosen the bolt on the operator output arm Power up set the mode switch to Hold Open and repeat the procedure from step 15 Install Door Arm Assembly Inswing Door Do not wear rings watches or loose clothing while i...

Page 16: ...essing other end of track onto track bracket 10 Press the other end of the track onto the track bracket as shown in Fig 19 and assemble using the two 1 4 20 x 9 16 flat head screws supplied 11 Tighten the screws fully 12 Assemble the pin into the door arm 13 Assemble the door arm and pin assembly into the slide block in the door track 14 Assemble the door arm onto the operator output shaft Do not ...

Page 17: ...for each specific application Shut off power at a circuit breaker or unplug the operator before making any changes to wiring Power Requirements See Fig 20 for proper location of concealed wiring 117 VAC 15 Amp service for one or two operators Dedicated 20 Amp service for three or four operators If an electrical cord is used to power the operator it must be UL Listed The electrical outlet and wire ...

Page 18: ...rams 2005 The STANLEY WORKS ALL RIGHTS RESERVED 203936 Rev C MA900 Installation Manual 16 Fig 22 Wiring diagram for single door with electric lock Fig 21 Wiring diagram for single door without lock factory wiring ...

Page 19: ... or other activating devices are needed between doors in a cccccvestibule they must be connected to the timing and sequencing module per the instructions provided with the module 4 Momentary electric strikes If using an electric strike that requires only a momentary contact to prevent overheating ccccca one shot relay may be needed Upon receiving an activating signal this type of relay provides an...

Page 20: ... right outswing or left inswing door rotate the cam count er clockwise ccw to increase clockwise cw to decrease the back check angle 6 On a left outswing or right inswing door rotate the cam cw to increase ccw to decrease the back check angle 7 Use the 3 32 Allen wrench to tighten the Allen screw 8 Power up 9 Test door operation by setting the mode switch to Hold Open or by using an external actua...

Page 21: ...rd specifies that doors be adjusted so that Closing time from 90 to 10 latch check is 3 sec or longer as stated in Table 1 The time from 10 to fully closed is not less than 1 5 sec Fig 27 Closeup of rheostat Closing time is controlled by the rheostat Use your fingers to rotate the rheostat knob ccw to increase cw to decrease the closing time see Fig 27 Adjust Opening and Closing Times Adjusting el...

Page 22: ...ccw to increase the opening time 2 CK back check time Back check time is the time it takes the door to move from the back check to fully open The time depends on the back check angle as specified on the previous page Turn the potentiometer ccw to increase cw to decrease the back check time 3 STL stall force The operator applies stall force to the door while it is being held open to prevent it from...

Page 23: ... On 2 A Power Close is Off B Power Close is On 3 A Magic Touch is On B Magic Touch is Off 4 A Power Close Cancel is Off B Power Close Cancel is On While Power Close is active the LED indicator is on and the Magic Touch feature is inactive Fig 31 Power Close potentiometers The Power Close feature is controlled by three potentiometers see Fig 31 1 TD3 Enable Time Delay Controls the time between the ...

Page 24: ... delay be set for a minimum of 5 sec Turn the potentiometer cw to increase ccw to decrease the Hold Open time 2 Hold Open Time Magic Touch TD2 controls the time interval from Magic Touch actuation to the start of the door close operation The time delay is adjustable from 1 30 sec The ANSI Standard requires that the time delay be set for a minimum of 5 sec Turn the potentiometer cw to increase ccw ...

Page 25: ... will help pedestrians to use the doors safely Decals Included The safety decal kit contains the items shown in Fig 35 below Fig 35 Safety decals Decal Placement Requirements The requirements set forth in the ANSI Standard A156 19 are summarized below All low energy doors shall be marked with signs one on each side of the door with the words CAUTION AUTOMATIC DOOR Each sign shall be mounted on the...

Page 26: ...sed to actuate the door operator the door shall be provided with signs on both sides with a message ACTIVATE SWITCH TO OPERATE The letter ing shall be white and the background shall be blue see Fig 36 When door motion is used to actuate the door operator Magic TouchTM the door shall be provided with the message PUSH TO OPERATE on the push side and the message PULL TO OPERATE on the pull side The l...

Page 27: ...Disconnect the door arm from the operator If door does not swing freely replace or repair worn or damaged door components and re install the door arm The door will not close or will not fully close 1 Is the Mode Switch set to HOLD OPEN Yes Set the Mode Switch to DAY No Step 2 2 Does wind or stack pressure keep the door from closing Yes Turn on the POWER CLOSE feature and re tune the operator No St...

Page 28: ...e bottom of the door Yes Remove obstruction No Step 2 2 Does the door operate freely when manually opened and closed Yes Contact authorized Stanley distributor for replacement No Verify door arm shoe outswing or track inswing location and re install if necessary Verify operator header mounting location and re install if necessary Disconnect the door arm from the operator If door does not swing fre...

Page 29: ... 2005 The STANLEY WORKS ALL RIGHTS RESERVED 203936 Rev C MA900 Installation Manual 27 Notes ...

Page 30: ... 2005 The STANLEY WORKS ALL RIGHTS RESERVED 203936 Rev C MA900 Installation Manual ...

Page 31: ... and operator control are already in this location The TDM layout and wiring connections are shown in Figure 1 Included on the following pages are detailed wiring and programming instructions for three common applications Figure 2 Simple Time Delayed Output Figure 3 Electric Lock Door Operator Sequencing Figure 4 Vestibule Door Sequencing After successfully wiring the TDM for your application refe...

Page 32: ...w mssedco com custsvc mssedco com Page 2 82A044 TDMv0605 FIGURE 1 TDM Layout Wiring Connections Input Connections Input Connections Wht Brown Wht Brown Wht Vio Wht Vio Wht Grn Wht Grn Wht Red Wht Red Wht Blue Wht Blue Blue Blue Green Green Green Green Wht Gray Wht Gray Input Power 12 24V Input Power 12 24V AC or DC AC or DC Switch Input 1 Switch Input 1 Switch Input 2 Switch Input 2 Switch Input 3...

Page 33: ...ting status Please refer to Figure 5 at the end of this installation manual or Electric Exit Device or Electric Exit Device Wall Wall Switch Switch PUSH PUSH TO TO OPEN OPEN WHT BLU WHT BLU BLU BLU MS SEDCO MS SEDCO TDM TDM Timing Control Module Timing Control Module N C N C Output 1 Output 1 Input 1 Input 1 SPRINKLER SPRINKLER OR FIRE OR FIRE DETECTION DETECTION SYSTEM SYSTEM IF USED IF USED FIRE...

Page 34: ...N The display should now read d4 Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode NOTE d1 should be longer than d3 3 You are now ready to test your installation If any of the time settings need to be changed make the change and press the PROGRAM MODE BUTTON once to save the new value Then wait 30 seconds until the double bars appear ag...

Page 35: ... double bars appear indicating that the unit is in its normal operating ready mode 3 You are now ready to test your installation If any of the time settings need to be changed make the change and press the PROGRAM MODE BUTTON once to save the new value Then wait 30 seconds until the double bars appear again indicating that the unit is in its normal operating mode 4 During operation of the unit the...

Page 36: ...y between d2 and d1 0 0 to 99 seconds i1 Switch Input 1 N O or N C i2 Switch Input 2 N O or N C i3 Switch Input 3 N O or N C i4 Switch Input 4 N O or N C o1 Relay Output 1 N O or N C o2 Relay Output 2 N O or N C Error flashing The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is stuck in the active position or if the wires have shorted If this occu...

Reviews: