Panel mounting devices
Series 8003/1
7.3.2 Cable Connection for Type 8003/1.1
Cable entry
Cable preparation
Conductor connection
• Use only cables with an outer diameter of 5 to 9 mm in the clamping
range of the cable entry.
• Comply precisely with the specified stripping length of the wires (6 mm)
in order to ensure the required creepage distances and clearances.
• Permanently install the cables and check that they are securely seated
when finished.
11612T00
• Push the cable into the cable
gland (1) from behind.
• Push the cable into the
connection chamber cover until
there is a sufficient length left
free on the other side to enable
connections to be prepared (2).
11613T00
• Strip 40 mm of the insulation of
the conductor.
• Strip 6 mm of the insulation of
the wires.
11614T00
11614T00
• Sectional view of the
terminal (1).
• Open the terminal with a
slotted screwdriver
(0.6 x 3.5 mm Form A
according to
DIN 5264/ISO 2380-1) (2).
The screwdriver blade
holds the terminal open,
thus enabling the conductor
to be introduced.
• Introduce the prepared
conductor (3).
• Remove the screwdriver.
• Check that the conductor
is seated securely.
The conductor is securely
clamped (4).