Emergency Luminaire with LED
Series EXLUX 6009/4
Ambient conditions
Ambient temperature
(1)
Rated operating time during emergency light operation
is guaranteed within an ambient temperature range of -5 to +50 °C.
This also applies to charging and discharging of the battery. The rated
operating time might be reduced if used outside this temperature range.
(2)
Battery service life
is guaranteed within an ambient temperature range of -30 to +50 °C
according to IEC/EN 60598-2-22.
Service life
LED Life Time
L
90
B
50
: 100,000 h
L
x
B
y
At the end of the service life:
• Luminous flux decline to "x" percent
• Up to "y" percent of all luminaires fall below "x"
Mechanical data
Material
Enclosure
Enclosure
polyester resin, glass fibre reinforced
Colour
Grey colour, similar to RAL 7035
Seal
Silicone seal, foamed into the translucent cover
Translucent cover Polycarbonate
Luminaire locking
Central lock for M8 / A/F 13 box spanner;
the translucent cover can be swivelled on its hinge
Mounting / Installation
Cable glands
Connection
Spring clamp terminals
Standard: 6-pole: L1, L2, L3, L', N, PE
with DALI: 8-pole: L1, L2, L3, L', N, PE, D1, D2
Clamping range:
1 x 1.5 to 6 mm
2
(solid / finely stranded)
(2 free clamping units per pole available)
Technical Data
without through wiring
-30 to +60 °C
(1, 2)
I
N
through wiring
(
10 A
-30 to +55 °C
(1, 2)
I
N
through wiring
(
16 A
-30 to +50 °C
(1)
Standard luminaire
Plastic:
2 x M25 x 1.5 cable entries 8161 and
2 x M25 x 1.5 stopping plugs 8290 (enclosed)
Metal:
2 x metal plates M20 x 1.5 connected by
means of PE for metal cable entries
Attention: cable entries must be ordered separately
Special
version:
max. 4 drilled holes for M20, M25, NPSM ½’’
max. 2 drilled holes for NPT ¾"
Metal cable glands: M20 x 1.5, M25 x 1.5;
earthing metal cable entries
using metal plates