Operation
30
265135 / 600960300190
2018-11-09·BA00·III·en·00
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Emergency Luminaire with LED
Series EXLUX 6009/4
10.3 Indications
When connecting to the power supply
Initialisation within 10 seconds
Then the LED indicator switches to operating mode.
During power supply operation
Blinking: 1 second on, 1 second off
Flashing: 0.25 seconds on, 0.75 seconds off
During emergeny light operation
The LED indicator is switched off.
Second
Description
0 to 2
Function test green LED
2 to 4
Function test red LED
4 to 10
Status rated operating time test
Green LED flashes - rated operating time test active
Green LED off - rated operating time test not active
Green
Luminaire is ready
for operation
Blinking green
Luminaire is ready
for operation
Function and rated operating time test activated
Red
Error
Battery is defective or electric circuit is interrupted
Blinking red
Error
Last function and/or rated operating time test faulty
Flashing red
Error
LEDs defective
Blinking
green/red
Luminaire is ready
for operation, no emergency
light operation
Emergency light operation is deactivated by
remote switch
Flashing
green/red
Luminaire is ready
for operation
Reset signal detected