265135 / 600960300190
2018-11-09·BA00·III·en·00
Technical data
9
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Emergency Luminaire with LED
Series EXLUX 6009/4
5
Technical data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx IBE 16.0038
Ex db eb ib mb op is IIC T4 Gb
Ex tb op is IIIC T100°C Db
Europe (ATEX)
Gas and dust
IBExU 16 ATEX 1199
E
II 2 G Ex db eb ib mb op is IIC T4 Gb
E
II 2 D Ex tb op is IIIC T100°C Db
Certifications and certificates
Certificates
IECEx, ATEX
Technical Data
Electrical data
Rated operational
voltage
AC: 110 to 230 V ±10 %; 50 to 60 Hz
Rated operational
current
Power factor
Rated insulation
voltage
250 V
THD
Size 2: < 15 %
Size 4: < 8 %
Inrush current
I
peak
= 63 A; Δt = 115
m
s
maximum number of luminaires per miniature circuit breaker at 230 V:
Size 2
Size 4
At nominal voltage
110 V
230 V
110 V
230 V
During stand-by
switching mode
< 0.08 A
< 0.08 A
< 0.08 A
< 0.08 A
In continuous mode
0.24 A
0.13 A
0.43 A
0.21 A
Size 2
Size 4
At nominal voltage
110 V
230 V
110 V
230 V
)
0.98
)
0.90
)
0.99
)
0.95
Type
10 A
16 A
20 A
25 A
B
7
11
14
17
C
11
19
23
29
K
23
38
47
59