Zone 2 Ex i Field Device Coupler 8 Spurs
Series 9411/24
Direct:
• Mount the shield bus on the field bus coupler
(see the chapter "Mounting the shield bus").
• Connect the shield bus to the earth via the shortest possible route.
Connect the green/yellow cable (contained in the scope of delivery for the shield bus)
and connect the device to the earth using an earth bolt.
• Lay the cable shields on the shield bus.
19391E00
6.5
EOL Resistor (Terminator)
An EOL resistor is required at both ends of the trunk. Spurs are operated without an
EOL resistor.
A trunk EOL resistor is permanently installed in every field device coupler.
To activate the trunk EOL resistor, the jumper is removed from the park position on the
field device coupler and connected to the terminals on the "TERM" terminal block.
If the field device coupler is located at the end of the trunk, i.e. the terminals on the
"TRUNK OUT" terminal block are not being used, the EOL resistor must be activated by
inserting the jumper at the "TRUNK" terminal block.
If the field device coupler is not located at the end of the trunk, i.e. the terminals on the
"TRUNK OUT" terminal block are being used, the terminals at the "TRUNK" terminal
block must not be bridged. The EOL resistor remains in the park position.
7
Transport and Storage
• Transport and store the device only in the original packaging.
• Store the device in a dry place (no condensation) and vibration-free.
• Do not drop the device.