Mounting:
- Carefully remove the cover (1) of the mounting slot (3) using a screwdriver or a knife.
- Carefully insert the auxilary contact (2) into the mounting slot until it engages.
- Paste the circuit diagram indicating the respective switching function to the rating plate
of the switch.
Dismounting:
- Insert auxiliary contact key (art. No. 201909) with the Stahl logo side up (!) between
the auxiliary contact and the switch cover.
- Pull out the auxiliary contact together with the auxiliary contact key.
Mounting the cover for Ex i auxiliary contact
12436E00
Fig. 7-6: Mounting the cover for Ex i auxiliary contact
- Attach the cover (4) from the top on the auxiliary contact until it engages into the lug.