147924 / 8537608300
2014-01-13·BA00·III·en·04
Technical data
13
Safety switch
8146/5-V37 8150/5-V37
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
1)
Engineering note:
The maximum conductor cross-sections given were determined using the H07V.
The minimum bending radius was assumed to be 4 x outer diameter in accordance with
VDE 0298-3.
2)
only with heat-resistant cable > 70 °C on cable entries or/and > 85 °C on clamping
points
Service life of
electrical /
mechanical
parts
> 10
5
operations
Max. short-cir
-
cuit protection
25 A, triggering characteristics: gG acc. to IEC/EN 60291-1
Auxiliary contacts
Electrical data
Rated operat
-
ing voltage
500 V AC
Rated opera
-
tional current
10 A
Mechanical data
Switch
3-pole: 1 NO (ON delayed - OFF advanced)
6-pole: 2 NO (1 x ON delayed - OFF advanced / 1 x switching nor
-
mally)
Mounting / Instal
-
lation
Terminals
1.5 / 1.5 ... 4 / 6 mm
2
finely stranded / solid wire
Ambient conditions Safety switches 16 A
Type
8146/5-V37-/
No. of poles
max. current
[A]
Conductor
cross-section
1)
[mm
2
]
Temperature class /
Perm. ambient
temperature
Main con
-
tacts
Auxiliary
contacts
Min.
Max.
302-...
3
1
16
2.5
6
T6: -40 ... +51 °C
T6: -40 ... +54 °C
2)
T5: -40 ... +69 °C
2)
602-...
6
2
16
2.5
6
T6: -40 ... +47 °C
T5: -40 ... +62 °C
2)
Type
8150/5-V37-
302-...
3
1
16
2.5
6
T6: -40 ... +40 °C
T6: -40 ... +65 °C
2)
Technical data