EN
8.4
Electrical Connection
- Fit the end covering sleeves using a suitable tool.
- Be especially careful when connecting the cable.
- The conductor insulation must reach to the terminal.
- The conductor itself must not be damaged when removing the insulation.
- Select the cables and the mode of running them in a way that the maximum permitted
cable temperature is not exceeded.
- Always connect the earth lead.
- Observe the tightening torque of the terminals.
Connection cross-section
8146/5-V37-.00-....
8146/5-V37-.01-....
Main contacts and auxiliary contacts (directly on the switch)
WARNING
Incorrectly installed components!
If the components are installed incorrectly, explosion protection is no
longer guaranteed.
Carry out installation strictly according to the instructions and national
safety and accident prevention regulations (e.g. IEC/EN 60079-14).
Connection
cross-section
1.5 ... 4 mm
2
solid
1.5 ... 2.5 mm
2
finely
stranded
Tightening
torque
1.8 Nm (16 lb-in)