Commissioning
10
200128 / 8006603300
2021-10-27·BA00·III·en·10
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Load and motor switch/
control switch
Series 8006/4
7
Commissioning
Before commissioning, carry out the following checks:
▶
Check the enclosure for damage.
▶
Check that mounting and installation have been performed correctly.
▶
Remove any foreign objects.
▶
Ensure correct, secure fit of the device and clamping connections.
▶
Check whether coverings are installed securely on live components.
▶
Check whether all the specified tightening torques have been observed.
8
Operation
The switch is operated using an axle and thereby actuates the contacts.
9
Maintenance, Overhaul, Repair
▶
Observe the relevant national standards and regulations in the country of use,
e.g. IEC/EN 60079-14, IEC/EN 60079-17, IEC/EN 60079-19.
9.1
Maintenance
Check the following points in addition to the national regulations:
• Whether the clamping screws holding the electrical lines fit securely
• Whether the device enclosure and/or protective enclosure has/have cracks or other visible
signs of damage
• Whether the permissible temperatures are complied with
• Whether the parts are securely fitted
• Whether the device is free of dust and coarse dirt
• Ensure it is being used as intended.
9.2
Overhaul
▶
Perform overhaul of the device according to the applicable national regulations and the
safety notes in these operating instructions ("Safety" chapter).
9.3
Repairs
▶
Perform repairs to the device only with original spare parts and after consultation with
R. STAHL.
DANGER! Overheating and explosion hazard due to defective switching contacts!
Non-compliance results in fatal or severe injuries.
▶
Replace the switch after each short circuit in the main circuit (the element is
hermetically sealed and the state of the switching contacts cannot be checked).
Summary of Contents for 169545