9
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Load and motor switch/
control switch
Series 8006/4
14288E00
Connection type
Connection terminals
Connection
cross-section
Solid/finely
stranded
1.5 to 6.0 mm
2
(10 mm
2
solid)
One or two conductors can be installed under one connection terminal.
Both conductors must have the same cross-section and must be made of the
same material. The conductors can be connected without any special prior
measures.
In case of different conductor cross-sections 1.5 to 6 mm
2
solid/finely stranded,
only 1 conductor each of the different conductor cross-sections may be installed
under the connection terminal. The conductors must be made of the same
material.
Only the following combinations are allowed:
1.5 and 2.5 mm
2
, 2.5 and 4 mm
2
and 4 and 6 mm
2
.
For jumpers, the following must be observed:
For jumpers of 4 mm
2
with core end sleeves only one additional conductor with a
conductor cross section of 2.5 or 4 or 6 mm
2
can be installed under the connection
terminal.
For jumpers of 4 mm
2
with core end sleeves and 2-way jumpers of 4 mm
2
with a
twin core end sleeve and core end sleeves, only one additional conductor with a
conductor cross section of 4 or 6 mm
2
can be installed under the connection
terminal.
10 mm
2
solid
Only one conductor, which must be bent in form of a hook (see drawing),
can be installed under the connection terminal.
Caution: Only possible without terminal cover!
15518E00
Tightening torque
2 Nm (connection terminals)
(applies to all connections)
10,5