SECTION FOUR – Routine Maintenance and Professional Servicing
LLLLooooccccaaaattttiiiioooonnnn
The Ignition Control Module is located in the Control
Box.
FFFFuuuunnnnccccttttiiiioooonnnn
The Ignition Control Module receives line voltage for
powering the Blower and Ignitor, and is sequenced by
low voltage supplied from the Operating Control Board
through the safety interlocks. It also supplies low-volt-
age power to the Combination Gas Valve.
SSSSeeeerrrrvvvviiiicccciiiinnnngggg PPPPrrrroooocccceeeedddduuuurrrreeee
To access the Ignition Control Module:
1. Turn off the pump and all electrical power to the
heater.
2. Unbolt and remove Upper Left and Upper Right
Jackets from the heater.
3. Open the Control Box cover by loosening the screw
on the top right side of the cover.
4. Disconnect all wires to the Ignition Control Module.
5. Remove the Ignition Control Module and replace it
with a new one.
6. Reconnect all wires to the Ignition Control Module
according to the connection diagram, Page 4-31.
7. Replace all covers and restart heater.
4-5
PR
ES
S
TA
B
VE
NT
PIL
OT
O
F
F
OFF
O
N
ON
Ignition Control Module
2687 1096
Ignition Control Module
SSSSaaaaffffeeeettttyyyy PPPPrrrreeeeccccaaaauuuuttttiiiioooonnnnssss::::
Hazardous voltage.
Both the Control Box
and the Ignition Control Module contain line voltage.
Disconnect the heater from the main power source
when servicing or replacing these parts.
Risk of control malfunction, overheat-
ing, possible fire or explosion.
Use
only
Sta-Rite
parts when replacing the Ignition Control Module.
P/N 42001-0052S