P/N S794
Rev. B 6-23-08
1 8
INDOOR VENTING — General Requirements
The heater may be installed as a Category I or Category III appliance.
Vented Appliance (Category I) –
Vertical only
An appliance that operates with a
nonpositive
vent static pressure and with a vent gas temperature that avoids excessive
condensate production in the vent, see
pages 20-22
.
Vented Appliance (Category III) –
Vertical or Horizontal
An appliance that operates with a
positive
vent static pressure and with a vent gas temperature that avoids excessive
condensate production in the vent, see
pages 23-25
.
If you are considering connecting this heater to a pre-existing vent system, make sure that the vent system meets the
appropriate venting requirements as given in this manual on
pages 18-27
. If not, replace the vent system.
DO NOT
use
a draft hood with this heater.
The vent pipe must be the same size or larger. The Max-E-Therm
®
heaters operate with a positive vent static pressure
and with a vent gas temperature less than 400° F. The total length of the horizontal run must not exceed the length that is
listed in
table 11
on
page 23
.
HEATER CLEARANCES — General Requirements
INDOOR INSTALLATION (U.S.) OR OUTDOOR SHELTER (CANADA)
The following clearances must be maintained from combustible surfaces:
TOP .............................. 6 in. (15 cm)
ALL SIDES .................. 6 in. (15 cm)
VENT ............................ 6 in. (15 cm)
Note:
The heater is design certified by CSA International for installation
on combustible flooring. For installation on carpeting, the heater must be
mounted on a metal or wood panel that extends at least three inches
(10cm) beyond the base of the heater. If the heater is installed in a
closet or alcove, the entire floor shall be covered by the panel. On an
outdoor shelter installation, the exhaust discharges into a vent pipe.
Orient the heater so that the vent pipe does not interfere with adjustment
of the operating controls. The operating control panel, located on the top
of the jacket, can be rotated for convenient access to the control panel.
OUTSIDE VENT COVER REMOVAL
The heater is supplied from the factory with a built-in stackless outside
vent for outdoor installation. Remove the outside vent cover for outdoor
shelter installation.
Section 2. Installation
6 in.
6 in.
6 in.
6 in.
ON
SP
A
Figure 12.