SSP North AB
30/08/2018
Manual V2f
127
This block is intended for setup and maintenance. The block creates a pulse from an input signal. It
ensures that the output is never high for longer than the specified Max Pulse Length time. After a
pulse has been generated, another one cannot be generated until the specified Min Low Time (ms)
has passed. If the input goes low before the specified Max Pulse Length time has passed, the output
goes low and another pulse cannot be generated until the specified Min Low Time has passed.
Inputs
•
Input
The input that should generate the pulse.
Outputs
•
Output
Outputs the generated pulse.
Properties
•
Comment
Changes the comment text above this block.
•
Max Pulse Length (ms)
The maximum length of the pulse. The pulse is never longer than this.
•
Min Low Time (ms)
The output is low for this time before a new pulse can be generated.
14.4.6 Internal Input
Block Diagram
Description
This block can be used to combine several signals as an input internally. The function behaves the
same way as a regular input function, but instead of using physical pins on the device it uses internal
signals. This can be used to for example synchronize two separate two-hand device inputs operated at
two different locations to ensure that they are pressed within a certain time, or to synchronize two or
more global memories from other units.
Note
See chapter 13.11 Input Functions on page 89, and chapter 14.1.4 Advanced Input on
page 109, for descriptions on how the input function works.