Flow-X─ Function Reference
5-327
Flow-X IO Functions - fxResetPulseInputErrors
fxResetPulseInputErrors
This function resets the error pulse counters (error, added, missing and simultaneous pulses) of the
pulse input of one of the modules part of the same configuration.
It is required that the pulse input of the specified module is configured by function 'fxPulseInput'.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag description
and tag group
<Empty>
Module
Unused, set to 0
0..16
0
Index
Index number as defined in the
corresponding fxPulseInput function
0 disables the function
0..1
Reset
0:
No action
<> 0
All error counters are reset to
0
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range or in
conflict
-
STS
FIOOR
Summary of Contents for flow-x