4-298
Flow-X─ Function Reference
Flow-X General functions - fxTotalizerDelta
fxTotalizerDelta
Description
The function accumulates a flow increment into a cumulative (eternal) total.
Besides of the cumulative total the function also outputs the flow increment that represents the
increase in flow quantity in the last calculation cycle. This increment value serves as an input for related
batch and period flow-weighted averaging and totalization functions.
Note: As opposed to the flow increment input value, the flow increment output
value is set to 0 when the totalization is disabled and has the proper units and is
therefore better suited as input for other functions.
Inputs and outputs
Function
inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag description
and tag group and retentive storage.
Flow
increment
Actual flow increment to be
accumulated.
Negative values will be ignored, so
the cumulative total will not
decrease.
Defined by
'Input unit'
0..1e11
Enabled
Dictates whether the flow
accumulation is enabled or not.
When disabled the cumulative total
will not be updated and the
increment will be set to 0.
0: Disabled
1: Enabled
EN
Input unit
Unit of input 'Flow increment'.
Output unit
Unit to be used for total and
increment.
Refer to the next section 'Unit
conversion' for more information.
Changing the unit will only be
possible when the cumulative total
value equals 0.
Rollover value
The cumulative total will be reset to
0 when it reaches the rollover value
Defined by
'Output
unit'
ROVAL
0..1e15
1e12
Decimal places
Defines the number of decimal
places for the total and increment
output values.
-1 means full precision (no rounding
applied)
DECPLS
-1..10
-1
Reset
This should be used with great care!
Command to reset the cumulative
total to 0
0: No reset
1: Reset
0
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Cumulative
total
Total quantity accumulated
so far since the last rollover
or reset
Defined by
'Input unit'
CUM
Increment
Increment in last
Defined by
INCR
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...