16.1.2 Display of system error
System errors consist of the message text "system error" and a 5-digit number in hexadecimal
code. The meaning of the individual error codes is described in the following table. If several
errors occur at the same time, the hexadecimal sum of the individual errors will be displayed.
The errors are coded in such a way that the individual errors can be easily identified. The
sums are unique.
Descriptor label
(never displayed)
Constant/
display
Description
SystemfehlerExtEEProm
0x00002
External EEPROM (data memory chip DSM)
plugged in but empty, not initialized
SystemfehlerIntEEProm
0x00004
Internal EEPROM (calibration UMF2 (B)
transmitter) erased, UMF2 uncalibrated
SystemfehlerEEPROM
0x00010
Unsuccessful saving or reading of memory
data / defective memory
16.1.3 Reset system error
After the fault recovery the displayed system error message can be reset.
For this purpose the customer password has to be entered. (Refer to 15.2.1 Customer-
password).
Select the function Show system error. (Refer to 15.11.10 Show system error).
Analyse the fault and repair the transmitter or sensor.
Finally reset the system error message. (Refer to 15.11.11 Reset system error)
General standards and directives
EN 60529
Degrees of protection provided by enclosures (IP code)
EN 61010-1:2010 Safety requirements for electrical equipment for measurement, control,
and laboratory use.
NAMUR guideline NE21, Version 2012-05-09
Directive 97/23/EC (Pressure Equipment Directive)
AD-2000 Guidelines
Electromagnetic compatibility
EMC Directive 2004/108/EC
EN 61000-6-2:2005
(immunity for industrial environments)
EN 61000-6-3:2007 +A1:2011 (emission standard for residential,
commercial and light-industrial environments)
EN 55011:2009 +A1:2010
group 1, class B
(emitted interference)
DIN EN 61326-1:2013
17. Standards & Directives