1-6
Chapter 1: Module Overview
User’s Manual Pub. 0300306-02 Rev. B
Table 1-3. Safety Test Specification Table
Safety Tests
Industry Standards
UL Safety
UL 61010-2-201 Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use - Part 2-201: Particular
Requirements for Control Equipment (NRAQ, NRAQ7)
CAN/CSA C22.2 No. 61010-1-12 (Safety Requirements for Electrical
Equipment for Measurement, Control,
and Laboratory Use – Part 1: General Requirements)
UL Hazardous
Locations
ANSI/ISA–12.12.01 Nonincendive Electrical Equipment for Use in Class I,
Division 2 Hazardous (Classified) Locations (NRAG)
CSA C22.2 No. 213-M1987 - Non-incendive Electrical Equipment for use in
Class I Division 2 Hazardous Locations - March 1987 (NRAG7)
Temp code T4 or better, Pollution degree 2, gas groups a,b,c, & d
CE EMC Directive
EN 61131-2 Programmable Controllers: Third Edition 2007-02, Clause 8,
Zones A&B
EN 61000-6-2: Generic Industrial Immunity
EN 61000-6-4: Generic Industrial Emissions
UKCA
Electromagnetic Compatibility Regulations 2016
BS EN 61131-2, BS EN 61000-6-4, BS EN 61000-6-2
FCC
27 CFR Part 15, Class A
ROROC
Arrêté ministériel n° 6404-15 du 29 ramadan 1436 (16 juillet 2015)
NM EN 61131-2, NM EN 61000-6-4, NM EN 61000-6-2
Section 1.3
Data Formats
There are four data input types:
•
Engineering units ×1
•
Engineering units ×10
•
Raw/proportional count
•
Percent Range
Section 1.4
Hardware
Features
Channels are wired as differential inputs. Open-circuit detection is available in
the form of open circuit inputs going over-range for the voltage and current
ranges. Inputs are protected from electrostatic discharge up to 6 kV for indirect
and contact discharge, 8 kV for air discharge. Inputs are also fault-protected up to
28 VDC for voltage inputs, and up to 32 mA for current inputs.
1.4.1
LED Blink Codes
Revision 1.1 and Revision 2.1 of the Module firmware use different LED status
operations for module status or power indication. Tables for 1.1 and 2.1 LED
Summary of Contents for Micro800 2085sc-IF16C
Page 1: ...User s Manual Pub 0300306 02 Rev B...
Page 8: ...vi Micro800TM 16 Channel Analog Input Module User s Manual Pub 0300306 02 Rev B...
Page 18: ...1 10 Chapter 1 Module Overview User s Manual Pub 0300306 02 Rev B...
Page 54: ...3 28 Chapter 3 Configuring the 2085sc IF16 Using CCW User s Manual Pub 0300306 02 Rev B...